6. CONTROL OUTLINE
Control Specifications
No.
1
2
3
Item
When power
supply is reset
Operation
mode selection
Room temp.
control
Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are
distinguished and the control is selected according to the
distinguished result.
2) Setting of indoor fan speed and existence of air direction
adjustment
Based on EEPROM data, select setting of the indoor fan
speed and the existence of air direction adjustment.
3) If resetting the power supply during occurrence of a
trouble, the check code is once cleared. After ON/OFF
button of the remote controller was pushed and the
operation was resumed, if the abnormal status continues,
the check code is again displayed on the remote controller.
1) Based on the operation mode selecting command from the
remote controller, the operation mode is selected.
Remote
controller
command
STOP
FAN
COOL
DRY
HEAT
AUTO
(
Heat recovery
system outdoor
unit type
)
Control outline
Air conditioner stops.
Fan operation
Cooling operation
Dry operation
Heating operation
• TA and Ts automatically select COOL/
HEAT operation mode for operation.
• The operation is performed as shown in
the following figure according to TA value
at the first time only.
(In the range of Ts – 1 < TA < Ts + 1,
Cooling thermostat OFF (Fan) / Setup air
volume operation continues.)
∗
Only
Heat recovery system outdoor unit type
can
select
automatic mode.
While
a wireless remote controller is
used, the mode is
notified
by “Pi Pi” (two times) receiving
sound
and the
alternate flashing of [TIMER ] and
[READY ].
To clear the alternate flashing, change the
mode on the
wireless remote controller.
1) Adjustment range: Remote controller setup temperature (˚C)
Remarks
TA: Room temp.
Ts: Setup temp.
∗
For
Heat recovery
system outdoor unit
type
Cooling thermostat OFF
(at the first time only)
Cooling
thermostat ON
Heating
thermostat ON
TA
(˚C)
–1.0
Ts
+1.0
Wired type
Wireless type
COOL/DRY
18 to 29
17 to 30
HEAT
18 to 29
17 to 30
AUTO
∗
18 to 29
17 to 30
- 68 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...