No. Part name
Procedure
Remarks
Fan motor,
Fan,
Ferrite core attached in earth
lead of motor
NOTE
When the ferrite core is attached to the earth wire
of a fan motor as below photo, please repairing
work indicated to P9
4
~
97
.
7)
Hook the fan assembly on the looser
screw B
.
8)
9)
Tighten the
screw A
and B.(M8 x 20, 10 pcs)
A ferrite core is attached to the wire of a fan motor as
before within an electric part box.
Connect the wires of the fan motor as before, and close
and fix the electrical parts box cover.
Be sure to wire in the electrical parts box as before.
2. Attachment
1) Screw the fan motor with the motor fixing plate.
(M8 x 20, 2 pcs).
NOTE
Fix the wiring of the motor on the
electrical parts
box side as right figure.
2) Attach the earth screw.
3) Put the fan in the fan case.
Attach the nose plate to the original position on the fan
case.
NOTE
Adjust the direction of the fan blade.
4) Insert the fan to the shaft.
5) Tighten the Screw C. (M8 x 20, 8 pcs)
6) Insert the fan to where the shaft of the fan motor stops,
and adjust the flat portion(2 places) ,
then tighten the
hexagon
head bolt.
NOTE
Check that if the fan rotate smoothly without
touching the fan case.
NOTE
Be sure to use a torque wench for fixing and tighten
with 10.0N
•
m
flat portion
flat portion
Hexagonal bolt
shaft
Fan blade
Electrical
parts box
Wiring of
the motor
Ground
screw
Ferrite
core
Wires of
the fan
motor
CN703
CN704
CN705
Ferrite
core
⑥
- 204 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...