No. Part name
Procedure
Remarks
Fan motor,
Fan,
Fan case
1.
Detachment
1)
Perform works until opening of the electric parts box
cover in works of 1 of
②
.
2)
Remove connectors for fan motor wiring from control
P.
C. board.
CN333 : Motor power supply (5P: White)
3)
Remove the fixing screws(Ø4x 8, 2 pcs.) of the fixing
plate.
4)
Remove the screw C from the fan case (under),open
and remove it while pressing claws of
both sides of the case.
5)
Remove a fixing screw of ferrite core and unscrew a
grounding only for AP036Type.
6)
Remove the fixing screws (Ø5 x 10, 2 pcs.) of the motor
band (2 pcs.) at the side of the fan motor.
(The fan motor becomes temporal hanging status by
fixing plate.)
7)
While supporting the fan motor by hands,remove the
fixing plate from the motor base to remove the fan
motor.
8)
Loosen the hexagonal screw hole of the fan and then
pull out the fan from the shaft.
(Hexagon wrench : 3mm)
9)
Remove the fixing screws(Ø4x 10, 6 pcs.) of the fan case
(upper)
And remove the fan case (upper).
2. Attachment
1) Attach the fan case (upper)as original position with the
fixing screws (Ø4x 10, 6 pcs.) .
2) Insert the fan in the shaft while adjusting to match the
hexagonal screw hole to the groove of the shaft.
3) Perform screwing the fan motor with the motor band
(Ø5 x 10, 2 pcs.)
4) While positioning so that the fan is at the center of the
fan case (upper), fix the fan with hexagonal screw.
5) Attach the fan case (under) as original and check the
fan turns smoothly without coming to contact with the
fan case,and fix the fan case (under) with screw C.
6)Attach the fixing plate as original position.
7) Connect the fan motor wirings as before,close and fix
the electric parts box cover.
Be sure to perform wirings as original in the electric
parts box.
8) Attach the suction panel as original position.
U
P036 type only
Fan case (under)
Fixing screw
Fixing screw
U
P036 type
U
P018 type
NOTE
Match the fan motor with turning direction of the fan
and fix so that t
he
U
P018 type and
U
P036 type is at
opposite side refrigerant piping.
NOTE
Be sure to use a torque wrench for fixing and tighten
with 4.9N
・
m or more.
Refrigerant
piping side
Screw with
hexagonal hole
Fixing plate
Screw C
Motor band
Screw
Ferrite core
Fan case
(under)
⑥
- 197 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...