<RBC-AMT
>
Step 1
Push
, and buttons on the remote controller simultaneously for more than 4 seconds.
* In the group control operation, the unit No. displayed for the first time is the header unit No..
At this time, the CODE No. (DN) shows “
10
”. Also, the fan of the indoor unit selected starts its
operation and the swing operation starts if it has the louvers.
(The unit No. “
ALL
” is displayed if the auto-address setting mode is interrupted in [2] step 2 a))
Step 2
Every time when
UNIT LOUVER
(left side button) button is pushed, the indoor unit No. in the group control
operation are displayed in order.
(The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set
values.)
Specify the indoor unit No. with its P.C. board replaced to the P.C. board for indoor unit servicing.
(You cannot perform this operation if “
ALL
” is displayed.)
Step 3
Select the CODE No. (DN) can be selected by pushing the
/
button for the temperature
setting.
• Set the indoor unit type and capacity.
The factory-set values shall be written to the EEPROM by changing the type and capacity.
3 6 5 1
4 2
Step 4
Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1
and 2 above again.
Step 5
Change the CODE No. (DN) to “
01
” by pushing
/
buttons for the temperature setting.
(this is the setting for the filter sign lighting time.)
Step 6
Check the setting data displayed at this time with the setting data put down in [1].
1. If the setting data is different, modify the setting data by pushing
/
buttons for the timer
setting to the data put down in [1].
The operation completes if the setting data is displayed.
2. If the data is the same, proceed to next step.
Step 7
Change the CODE No. (DN) by pushing
/
buttons for the temperature setting.
As described above, check the setting data and modify to the data put down in [1].
Step 8
Repeat the steps 6 and 7.
Step 9
After the setting completes, push button to return to the normal stop status.
(It takes approx. 1 min until the remote controller operation is available again.)
* The CODE No. (DN) are ranged from “
01
” to “
FE
”. The CODE No. (DN) is not limited to be
serial No.
Even after modifying the data wrongly and pushing button, it is possible to return to the data
before modification by pushing button if the CODE No. (DN) is not changed.
1. Set the CODE No. (DN) to
10
. (without change)
2. Select the type by pushing
/
buttons for the timer setting.
(For example, 4-way Cassette Type is set to “
0001
”. Refer to
table 2)
3. Push button.
(The operation completes if the setting data is displayed.)
4. Change the CODE No. (DN) to “
11
” by pushing
/
buttons for the temperature setting.
5. Select the capacity by pushing
/
buttons for the timer
setting.
(For example, UP018 Type is set to “
0009
”. Refer to table 3)
6. Push button.
(The setting completes if the setting data are displayed.)
- 166 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...