In case of wireless remote controller
1
Turn on the power of the air conditioner.
When power is turned on for the first time after installation, it takes approx. 5 minutes until the remote
controller becomes available. In the case of subsequent power-on, it takes approx. 1 minute until the remote
controller becomes available.
Execute a test run after the predetermined time has passed.
2
Push “ON/OFF” button on the remote controller, select [
Cool ] or [
Heat ] with “MODE” button, and
then select [
HIGH ] with “FAN” button.
3
Cooling test run
Heating test run
Set the temperature to 17 ˚C
with the temp. setup buttons.
Set the temperature to 30 ˚C
with the temp. setup buttons.
Cooling test run
Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 18 ˚C with
the temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 29 ˚C with
the temp. setup buttons.
Cooling test run
Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 17 ˚C with
the temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 30 ˚C with
the temp. setup buttons.
4
5
6
Repeat procedures
4
o
o
o
o
o
5
o
o
o
o
o
4
o
o
o
o
o
5
.
Indicators “Operation” (green), “Timer” (green), and “Ready” (orange) in the wireless receiver section flash
in approx. 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash,
repeat procedures 2 to 5.
7
Upon completion of the test run, push “ON/OFF” button to stop operation.
<Overview of test run operations using the
wireless remote controller>
Cooling test run:
ON/OFF
o
17 °C
o
18 °C
o
17 °C
o
18 °C
o
17 °C
o
18 °C
o
17 °C
o
(test run)
o
ON/OFF
Heating test run:
ON/OFF
o
30 °C
o
29 °C
o
30 °C
o
29 °C
o
30 °C
o
29 °C
o
30 °C
o
(test run)
o
ON/OFF
- 96 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...