Item
Room temp.
control
(Continued)
Outline of specifications
2) Using the Item code 06, the setup temperature in heating
operation can be compensated.
Remarks
Shift of return air
temperature in heating
operation
Except while sensor of
the remote controller is
controlled
(Code No. [32], “0001”)
Setting at shipment
1) Based on the difference between TA and Ts, the opera-
tion capacity is determined by the outdoor unit.
Setup data
Setup temp. compensation
6
+6˚C
4
+4˚C
2
+2˚C
0
+0˚C
Model
Set data
Floor standing cabinet, Floor standing concealed,
Floor standing
Other models
0
2
Automatic
capacity control
Automatic
cooling/heating
control
1) The judgment of selecting COOL/HEAT is carried out as
shown below. When +1.5 exceeds against Tsh
10 minutes and after thermostat OFF, heating operation
(Thermostat OFF) exchanges to cooling operation.
Description in the parentheses shows an example of
cooling ON/OFF.
When –1.5 lowers against Tsc 10 minutes and after
thermostat OFF, cooling operation (Thermostat OFF)
exchanges to heating operation.
2) For the automatic capacity control after judgment of
cooling/heating, see Item 4.
3) For temperature compensation of room temp. control in
automatic heating, see Item 3.
Ts: Setup temp.
TA: Room temp.
∗
For
Heat recovery
system outdoor unit
type
Tsc:
Setup temp. in
cooling operation
Tsh: Setup temp. in
heating ope
temp. compensation
of room temp. control
TA
(˚C)
-1.5
Tsc
Tsh
+1.5
Heating
(Cooling OFF)
(Cooling ON)
or
Cooling
TA
(˚C)
+2
TA
(˚C)
+1
+1
Ts
Ts
–1
–1
–2
COOL
HEAT
S3
S5
S7
S9
SB
SD
SF
S0
SD
SB
S9
S7
S5
S3
S0
- 69 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...