No. Part name
Procedure
Remarks
1. Detachment
1) Recover the refrigerant gas and then remove the
refrigerant pipe of the indoor unit.
2) Perform 1 of
⑧
.
3) Perform 1 of
⑨
.
4) Remove the screws (M8 x 20, 5 pcs) and remove
the right side panel.
5) Remove the screws (M8 x 20, 4 pcs) and remove
the evaporator partition (back).
6) While holding the heat exchanger, remove the fixing
screws (M8 x 20, 5 pcs) of the fixing end plate (UP)
and evaporator partition (DOWN) and then take out
the heat exchanger slowly.
Heat
exchanger
Sensor
TC1,TC2,TCJ
Fixing screws
Right side panel
Evaporator partition (back)
Fixing screws
1. Detachment
1) Perform 1 of
①
to open the electrical parts box cover.
2) Loosen the fixing screws of the inspection cover and
open the inspection cover.
3) Remove the connectors of the wires of TC1 sensor ,
TC2 sensor and TCJ sensor from the
control
P.C. board.
CN100 : TC1 sensor (3P: Brown)
CN101 : TC2 sensor (2P: Black)
CN102 : TCJ sensor (2P
:
Red)
2. Attachment
1) Attach the TC1 sensor , TC2 sensor and TCJ sensor to
the original position.
2) Wire the wires of TC1 sensor, TC2 sensor, and TCJ
sensor as before.
3) Attach the left side panel as before.
Heat exchanger
Screw
Inspection cover
Control P.C.board
MCC-1643
TCJ sensor
TC2 sensor
TC1 sensor
⑧
⑨
- 206 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...