Check code
Location
of
detection
Description
System status
Check code detection
condition(s)
Check items (locations)
• Check for connection
trouble involving Ps sensor
and Pd sensor connectors.
• Check connection of Ps
sensor connector.
• Check for failure in Ps
sensor.
• Check for compressor
poor compression.
• Check for failure in 4-way
valve.
• Check for failure in outdoor
P.C. board (I/F).
• Check for failure in SV4
circuit.
Ps sensor
trouble
I/F
All stop
Output voltage of Ps
sensor is zero.
F23
F23
—
• Check connection of Pd
sensor connector.
• Check for failure in Pd
sensor.
• Check for failure in outdoor
P.C. board (I/F).
Pd sensor
trouble
I/F
All stop
Output voltage of Pd sensor
is zero (sensor open-
circuited).
Pd > 4.15MPa despite
compressor having been
turned off.
F24
F24
—
• Check for failure in indoor
P.C. board (failure
EEPROM)
Other indoor
trouble
Indoor unit
Stop of
corresponding
unit
Indoor P.C. board does not
operate normally.
F29
—
—
• Check power supply
voltage.
• Check power supply noise.
• Check for failure in outdoor
P.C. board (I/F).
Outdoor
EEPROM
trouble
I/F
All stop *1
Outdoor P.C. board (I/F)
does not operate normally.
F31
F31
—
• Check power supply
voltage.
(AC380V-415V ± 10%).
• Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (Compressor).
Compressor
breakdown
Compressor
P.C. board
1
∗
: Compressor
1
side
2
∗
: Compressor
2
side
All stop
Inverter current detection
circuit detects overcurrent
and shuts system down.
H01
H01
• Check current detection
circuit wiring.
• Check failure in outdoor
P.C. board (Compressor).
Current
detection
circuit trouble
Compressor
P.C. board
1
∗
: Compressor
1
side
2
∗
: Compressor
2
side
All stop
Current flow of at least
specified magnitude is
detected despite inverter
compressor having been
shut turned off.
H03
H03
• Check for failure in
compressor.
• Check power supply
voltage.
(AC380V-415V ± 10%).
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on
compressor P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
problem inside
compressor.)
• Check for failure in outdoor
P.C. board (Compressor).
• Check outdoor MG-CTT.
Compressor
trouble (lockup)
MG-CTT trouble
Compressor
P.C. board
1
∗
: Compressor
1
side
2
∗
: Compressor
2
side
All stop
Overcurrent is detected
several seconds after
startup of inverter
compressor.
H02
H02
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
• Check connection of high-
pressure Pd sensor
connector.
• Check connection of low-
pressure Ps sensor
connector.
• Check for failure in
pressure sensors Pd and
Ps.
• Check for trouble in
outdoor P.C. board (I/F).
• Check for compressor
poor compression.
Outdoor
pressure
sensor wiring
trouble (Pd, Ps)
I/F
All stop
Readings of high-pressure
Pd sensor and low-pressure
Ps sensor are switched.
Output voltages of both
sensors are zero.
F16
F16
—
- 141 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...