No.
7
Part name
Fan motor
Procedure
1.
Detachment
1)
Carry out work of item 1 of
2
.
2)
Remove connectors which are connected from
the control P.C. board to the other parts and
then remove each wiring from the clamp.
CN510
:
Louver motor (20P, White)
CN34
:
Float switch (3P, Red)
CN504
:
Drain pump (2P, White)
CN100
:
TC1 sensor (3P, Brown)
CN101
:
TC2 sensor (2P, Black)
CN102
:
TCJ sensor (2P, Red)
CN104
:
Room temp. Sensor (2P, Yellow)
CN
2
10
:
Fan
motor
power supply (5P, White)
CN82
:
PMV (6P, Blue)
NOTE :
Unlock the lock of the housing part and then
remove the connector.
3) Remove the fixing screws A and B, and then
remove the electric parts box.
(Fixing screw A: Ø4 × 10, 3 pcs,
Fixing screw B: Ø4 ×
10
, 1 pc.)
4) Remove the fan motor lead, TC sensor and
TCJ sensor from clamp of the bell mouth.
5) Remove the fixing screws and then remove
the bell mouth. (Ø4 × 10, 8 pcs.)
6) Remove the fixing screws and then remove
the nut cap. (Ø4 × 10, 2 pcs.)
7) Remove the fixing nut and then remove the
turbo fan. (M8 nut with flange, 1 pc.)
8) Remove the fixing screws and then remove
the motor lead holding bracket.
(Ø4 × 8, 2 pcs.)
9) Cut the bundling band and then remove it
from the clamp.
10) Remove the fixing nut and then remove the
fan motor. (Ø6 nut, 3 pcs.)
2. Attachment
1) Fix the parts as before in order of fan motor
→
motor lead holding bracket
→
turbo fan
→
nut cap
→
bell mouth.
NOTE :
Fix the motor lead to the clamp without slack
as before using bundling band.
When fixing the turbo fan, be sure to match
the D-cut of the fan boss with D-cut of the
motor shaft.
Using a torque wrench, fix the turbo fan and
tighten it to 5.4 Nm.
Using torque wrench, fix the fan motor
(at 3 positions) and tighten it to 4.9 Nm.
Remarks
M8 nut with flange
Fixing screw A
Fixing screw
Turbo fan
Fixing screw B
Fixing screw B
Electric parts box
Clamp
TC sensor
TCJ sensor
Fan motor lead
Bell mouth
Nut cap
+0.5
–0.2
+0.5
–0.2
- 173 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...