No.
Part name
Procedure
Remarks
1.
Detachment
1)
Perform works until opening of the electric
parts box cover in works of 1 of
f
.
2)
Remove connectors for fan motor wiring
from control P.C. board.
CN333 :
Motor power supply (5P: White)
3) Open the fan case (under) and remove it
while pressing claws of the fan case
(under). (There are both sides of the case)
4) Remove the fixing screws (Ø5 x 10, 2 pcs.)
of the fixing plate (2 pcs.) at the side of the
fan motor.
(The fan motor becomes temporal hanging
status by fixing plate.)
5) While supporting the fan motor by hands,
remove the fixing plate from the motor base
to remove the fan motor.
6) Loosen the hexagonal screw hole of the fan
and then pull out the fan from the shaft.
(Hexagon wrench : 3mm)
2. Attachment
1) Insert the fan in the shaft while adjusting to
match the hexagonal screw hole to the
groove of the shaft.
2) Perform screwing the fan motor with the
fixing plate (Ø5 x 10, 2 pcs.)
NOTE
Match the fan motor with turning direction of
the
fan and fix so that the
U
P00
5
type and
U
P024
t
y
pe
fan motor wirings are at
refrigerant
piping
side and
U
P036
type is at
opposite side
of-refrigerant
piping.
3) While positioning so that the fan is at the
center of the fan case (upper), fix the fan
with hexagonal screw.
NOTE
Be sure to use a torque wrench for fixing and
tighten with 4.9N•m or more.
4) Attach the fan case (under) as original and
check the fan turns smoothly without
coming to contact with the fan case.
5) Connect the fan motor wirings as before,
close and fix the electric parts box cover.
Be sure to perform wirings as original in the
electric parts box.
6) Attach air filter and suction panel as
original position.
Fan motor,
Fan,
Fan case
Refrigerant
pip
i
ng side
U
P036 Type
U
P024 Type
U
P00
5
Type
CAUTION
When replacing the fan motor, be sure
to exchange the clamp filter with the
fan motor lead wire.
Fixing screw
Fixing sheet metal
Screw with
hexagonal hole
h
- 191 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...