[2] P.C. Board for indoor unit servicing replacement procedures (e.g. MCC-1643)
Connector (CN504)
for drain pump
Attach reactor's plug
to connector CN01
If the plug for short-circuit is attached on the P.C. board
before replacement, attach it on the P.C. board replaced.
CN34
(Red)
CN01
(BLU)
CN504
(White)
J01
J08
J09
SW501
Step1
Replace the P.C. board to the P.C. board for indoor unit servicing.
At this time, perform the same setting of the jumper wire (J01, J08, J09) setting (cut), switch
SW501, (short-circuit) connector CN34 as the setting of the P.C. board before replacement.
Step2
It is necessary to set indoor unit to be exchanged: Remote controller = 1 : 1
Based upon the system configuration, turn on power of the indoor unit with one of the following items.
1) Single (Individual) operation. Turn on power of the indoor units and proceed to [3].
2) Group operation
A) In case that power of the exchanged indoor unit only can be turned on
Turn on power of the exchanger indoor unit only and proceed to [3].
B) In case that power of the indoor units cannot be turned on individually (Case 1)
a) Remove temporarily the group wire connected to the terminal blocks A and B of the indoor
unit.
b) After connecting the remote controller wire only to the removed terminal block, turn on
power of the indoor units and proceed to [3].
* When the above methods cannot be used, follow to the two cases below.
C) In case that power of the indoor units cannot be turned in individually (Case 2)
a) Remove all CN41 connectors of the indoor units in the same group except those of the
exchanged indoor unit.
b) Turn on power of the indoor units and proceed to [3].
* After [3] operation has finished, be sure to return the temporarily removed group wire or
CN41 connector to the original connection.
Indoor unit
P.C. board
Service P.C. board of
the unit to be changed
Remote
controller
Group wire
(Case 1)
Remove the group wire
of the terminal blocks
A and B of the changed
indoor unit and then install
the remote controller only.
Remove CN41 connectors of the
indoor units other than the units
to be changed in the same group.
A B
Indoor unit
Indoor unit
A B
Remote
controller
A B
Indoor unit
P.C. board
Service P.C. board of
the unit to be changed
Group wire
(Case 2)
CN41
A B
A B
- 164 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...