background image

Installer reference guide 

Daikin room air conditioner

CTXM15R2V1B
CTXM15R5V1B

FTXM20R2V1B
FTXM20R5V1B
FTXM25R2V1B
FTXM25R5V1B
FTXM35R2V1B
FTXM35R5V1B
FTXM42R2V1B
FTXM42R5V1B

FTXM50R2V1B
FTXM60R2V1B
FTXM71R2V1B

ATXM20R2V1B
ATXM20R5V1B
ATXM25R2V1B
ATXM25R5V1B
ATXM35R2V1B
ATXM35R5V1B
ATXM50R2V1B

Summary of Contents for CTXM15R2V1B

Page 1: ...tioner CTXM15R2V1B CTXM15R5V1B FTXM20R2V1B FTXM20R5V1B FTXM25R2V1B FTXM25R5V1B FTXM35R2V1B FTXM35R5V1B FTXM42R2V1B FTXM42R5V1B FTXM50R2V1B FTXM60R2V1B FTXM71R2V1B ATXM20R2V1B ATXM20R5V1B ATXM25R2V1B A...

Page 2: ...24 6 2 2 To open the service cover 25 6 2 3 To remove the front grille 25 6 3 Mounting the indoor unit 26 6 3 1 To install the mounting plate 26 6 3 2 To drill a wall hole 27 6 3 3 To remove the pipe...

Page 3: ...43 9 4 To close the indoor unit 43 9 4 1 To re install the front grille 43 9 4 2 To close the service cover 43 9 4 3 To re install the front panel 43 10 Configuration 45 10 1 To set a different addre...

Page 4: ...safety precautions Safety instructions that you MUST read before installing Format Paper in the box of the indoor unit Indoor unit installation manual Installation instructions Format Paper in the bo...

Page 5: ...installer 2 1 1 Meaning of warnings and symbols DANGER Indicates a situation that results in death or serious injury DANGER RISK OF ELECTROCUTION Indicates a situation that could result in electrocut...

Page 6: ...erate the unit contact your dealer DANGER RISK OF BURNING SCALDING Do NOT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too...

Page 7: ...ase of an emergency Name and address of fire department police and hospital Name address and day and night telephone numbers for obtaining service In Europe EN378 provides the necessary guidance for t...

Page 8: ...e or an operating electric heater in case the floor area is less than the minimum floor area A m no auxiliary devices which may be a potential ignition source are installed in the duct work example ho...

Page 9: ...Outdoor units installed or stored indoors e g winter garden garage machinery room Pipework in unventilated spaces NOTICE Pipework shall be protected from physical damage Installation of pipework shall...

Page 10: ...2 0 3 95 5 6 19 9 2 0 34 0 5 6 267 2 2 4 34 5 8 21 3 2 2 41 2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76...

Page 11: ...essive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas might be produced if refrigerant gas comes into contact with fire DANGER RISK OF EXPLOSION Pump down Refriger...

Page 12: ...terials from entering into the system Charge the liquid refrigerant as follows If Then A siphon tube is present i e the cylinder is marked with Liquid filling siphon attached Charge with the cylinder...

Page 13: ...y complies with EU directive 98 83 EC 2 2 6 Electrical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical p...

Page 14: ...h leakage protector CAUTION When connecting the power supply connect the earth cable first before making the current carrying connections When disconnecting the power supply disconnect the current car...

Page 15: ...CE Only applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of reversed phase after a momentary black out and the power goes...

Page 16: ...irty or damaged CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire Piping in...

Page 17: ...wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equ...

Page 18: ...rted immediately to the claims agent of the carrier Bring the packed unit as close as possible to its final installation position to prevent damage during transport When handling the unit take into ac...

Page 19: ...thout frame e2 Class 50 71 Titanium apatite deodorising filter and silver allergen removal air purifying filter with frame f Indoor unit fixing screw M4 12L Refer to 9 3 To fix the unit on the mountin...

Page 20: ...and silver allergen removal air purifying filter with frame 5 2 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation In combination with ou...

Page 21: ...on instructions setting methods FAQ declaration of conformity and the latest version of this manual visit http www onlinecontroller daikineurope com INFORMATION Daikin Industries Czech Republic s r o...

Page 22: ...orted version of Android or iOS specified on http www onlinecontroller daikineurope com Internet line and communicating device such as modem router etc Wireless LAN access point Installed free Daikin...

Page 23: ...place In case of construction works e g grinding works where a lot of dust is created the unit MUST be covered Choose an installation location with sufficient space for carrying the unit in and out of...

Page 24: ...use it may shorten the life of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present In places where a mineral oil mist spray or vapour may be p...

Page 25: ...t a b a Service cover screw b Service cover NOTICE When closing the service cover make sure that the tightening torque does NOT exceed 1 4 0 2 N m 6 2 3 To remove the front grille CAUTION Wear adequat...

Page 26: ...g the indoor unit In this chapter 6 3 1 To install the mounting plate 26 6 3 2 To drill a wall hole 27 6 3 3 To remove the pipe port cover 28 6 3 1 To install the mounting plate 1 Install the mounting...

Page 27: ...ixing spots f Position for the tape measure at symbol b Pocket for the pipe port cover g Gas pipe end c Tabs for placing a spirit level h Liquid pipe end d Through the wall hole e Drain hose position...

Page 28: ...pipe port cover from inside the front grille using a coping saw 2 Remove any burrs along the cut section using a half round needle file NOTICE Do NOT use nippers to remove the pipe port cover as this...

Page 29: ...id polyvinyl chloride pipe When connecting a rigid polyvinyl chloride pipe nominal 13 mm directly to the drain hose as with embedded piping work use a field supplied drain socket nominal 13 mm a b c 1...

Page 30: ...or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insulation fixing screw on...

Page 31: ...18023 8G 2020 06 A B C b a A Left side piping B Left back piping C Left bottom piping a Remove the pipe port cover here for left side piping b Remove the pipe port cover here for left bottom piping 6...

Page 32: ...Preparing refrigerant piping 7 1 1 Refrigerant piping requirements INFORMATION Also read the precautions and requirements in the General safety precautions chapter NOTICE The piping and other pressur...

Page 33: ...sulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 10 14 mm 13 mm 12 7 mm 1 2 14 16 mm 13 mm 15 9 mm 5 8 16 20 mm 13 mm i i t p p If the temperature is higher than 30 C and the humidity is highe...

Page 34: ...into account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 when adding refrigerant Only use installation tools e g manifold gauge set that...

Page 35: ...ion d Flare nut Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm 6 4 15 17 8 7 9 1 R 0 4 0 8 2 45 90 2 A 9 5 33 39 12 8 13 2 12 7 50 60 16 2 16 6 15 9 62 75 19 3 19 7 7 2 4 Pi...

Page 36: ...MUST be evenly flared in a perfect circle c Make sure the flare nut is fitted 7 2 6 To connect the refrigerant piping to the indoor unit WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this...

Page 37: ...cal workflow Connecting the electrical wiring typically consists of the following stages 1 Making sure the power supply system complies with the electrical specifications of the units 2 Connecting the...

Page 38: ...LWAYS use multicore cable for power supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage...

Page 39: ...Flat washer O Allowed X NOT allowed The earth wire between the wire retainer and the terminal must be longer than the other wires 1 3 8 1 3 Specifications of standard wiring components Component Inter...

Page 40: ...ansmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Pro...

Page 41: ...8 Electrical installation Installer reference guide 41 CTXM15 FTXM20 42 ATXM20 35R2 5V1B FTXM50 71R2V1B ATXM50R2V1B Daikin room air conditioner 4P518023 8G 2020 06...

Page 42: ...n hose together using insulation tape Overlap at least half the width of the tape with each turn d e c b f a 2 a Drain hose b Interconnection cable c Mounting plate accessory d Refrigerant piping e In...

Page 43: ...the mounting plate using 2 indoor unit fixing screws M4 12L accessory 9 4 To close the indoor unit 9 4 1 To re install the front grille 1 Install the front grille and firmly engage the 3 upper hooks 2...

Page 44: ...9 Finishing the indoor unit installation Installer reference guide 44 CTXM15 FTXM20 42 ATXM20 35R2 5V1B FTXM50 71R2V1B ATXM50R2V1B Daikin room air conditioner 4P518023 8G 2020 06...

Page 45: ...cover and the batteries from the user interface 2 Cut the address jumper J4 a a Address jumper J4 NOTICE Be careful NOT to damage any of the surrounding parts when cutting the address jumper 3 Turn th...

Page 46: ...aikin room air conditioner 4P518023 8G 2020 06 INFORMATION If the setting could NOT be completed while the operation lamp was blinking repeat the setting process from the beginning 7 When the setting...

Page 47: ...ts cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Make sure drainage flows smoothly Possible conse...

Page 48: ...unctions and parts are working properly 1 In cooling mode select the lowest programmable temperature In heating mode select the highest programmable temperature Test run can be disabled if necessary 2...

Page 49: ...unit operates properly please make sure the following is clear for the user Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that h...

Page 50: ...room air conditioner 4P518023 8G 2020 06 13 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with appl...

Page 51: ...wiring diagram on the unit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit break...

Page 52: ...light emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil...

Page 53: ...gh S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector...

Page 54: ...r a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it M...

Page 55: ......

Page 56: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 4P518023 8G 2020 06 Copyright 20...

Reviews: