Unit Description
5-29
Zone 1 Cool and Zone 2 Heat T-800R/T-1000R/T-1200R SPECTRUM Units
The CIS is closed so high pressure refrigerant vapor leaves the compressor and flows into the hot gas lines.
The HGS2 is open so most of the refrigerant flows through it into the Zone 2 evaporator. There, the refrigerant heats the Zone
2 evaporator and condenses into high pressure liquid. Because the SLS2 is closed, the liquid refrigerant flows through the
LRCV2 and the liquid lines to the LLS1.
The LLS1 is open so the refrigerant flows through the Zone 1 heat exchanger and expansion valve into the Zone 1 evaporator.
There, liquid refrigerant absorbs heat as it evaporates into low pressure vapor. The refrigerant returns to the compressor
through the heat exchanger, SLS1, suction line, SLCV1, accumulator, and SPR/ETV.
Some of the refrigerant flows through the open RTPS and forces any liquid refrigerant out of receiver tank through the drier
and into the liquid lines, where it joins the liquid refrigerant going to the Zone 1 evaporator.
In the condensing unit, the CIS will open momentarily if necessary to control high discharge pressure. The PV is open
continuously during heat to drain the condenser coil.
Zone 1 Evaporator
1F. Zone 1 Liquid Line Solenoid (LLS1)-Open/ Energized
2F. Zone 1 Liquid Return Check Valve (LRCV1)-Closed
3F. Zone 1 Suction Line Solenoid (SLS1)-Open/ De-energized
4F. Zone 1 Suction Line Check Valve (SLCV1)-Open
5F. Zone 1 Hot Gas Solenoid (HGS1)-Closed/ De-Energized
Zone 2 Evaporator
1R. Zone 2 Liquid Line Solenoid (LLS2)-Open/ Energized
2R. Zone 2 Liquid Return Check Valve (LRCV2)-Open
3R. Zone 2 Suction Line Solenoid (SLS2)-Closed/ Energized
4R. Zone 2 Suction Line Check Valve (SLCV2)-Closed
5R. Zone 2 Hot Gas Solenoid (HGS2)-Open/ Energized
Condensing Unit
6. Condenser Inlet Solenoid (CIS)-Closed/ Energized but the microprocessor will open it if necessary to control high discharge
pressure.
7. Condenser Check Valve (CCV)-Closed
8. Receiver Tank Pressure Solenoid (RTPS)-Open/Energized
9. Purge Valve (PV)-Open/Energized
10. Purge Check Valve (PCV)-Closed
Solenoid Delays
Purge Mode delays the normal output of the CIS, HGS, and RTPS when the unit shifts from all zones in Cool (or Null) to any
zone in Heat or Defrost.
CIS Delay – When there is a requirement for the CIS valve to close (energize) and a HGS to open (energize), the CIS will
delay closing (energizing) for 5 seconds.
SLS Delay – When there is a requirement for an SLS valve to close (energize), the SLS will delay closing (energizing) for 120
seconds.
Summary of Contents for T-1000R
Page 14: ...Safety Precautions 2 6 Warning Decals 2e24151g0 ...
Page 34: ...Maintenance Inspection Schedule 4 10 ...
Page 57: ...Unit Description 5 23 Purge Mode UT Series 1 3 4 5 2 ...
Page 67: ...Unit Description 5 33 Zone 1 Cool and Zone 2 Cool UT SPECTRUM Units ...
Page 69: ...Unit Description 5 35 Purge Mode UT SPECTRUM Units ...
Page 71: ...Unit Description 5 37 Zone 1 Cool and Zone 2 Heat UT SPECTRUM Units ...
Page 72: ...Unit Description 5 38 ...
Page 74: ...Diesel Electric Menu 6 28 Adjust Brightness 6 29 Time 6 30 ...
Page 120: ...Operating Instructions Standard HMI 7 18 ...
Page 152: ...Engine Maintenance 9 14 T Series Fuel and Oil System Components TK 376 ...
Page 154: ...Engine Maintenance 9 16 T Series Fuel and Oil System Components TK 270 ...
Page 156: ...Engine Maintenance 9 18 UT Series Fuel System Components AMA768 ...
Page 172: ...Engine Maintenance 9 34 T Series Engine Mounting Components for 2 Cylinder Engine ...
Page 184: ...Engine Maintenance 9 46 ...
Page 238: ...Refrigeration Maintenance 10 54 ...
Page 246: ...Clutch Maintenance 11 8 ...
Page 258: ...Structural Maintenance 12 12 ...
Page 264: ...Mechanical Diagnosis 13 6 ...
Page 265: ...14 Electric Standby Diagnosis ...
Page 268: ...Electric Standby Diagnosis 14 4 ...
Page 269: ...15 Refrigeration System Diagnosis ...
Page 272: ...Refrigeration System Diagnosis 15 4 ...
Page 280: ...Remote Evaporators 16 8 ...