Unit Description
5-32
Zone 1 Cool and Zone 2 Cool UT SPECTRUM Units
High pressure refrigerant vapor leaves the compressor and flows through the open CIS to the condenser where the refrigerant
releases heat and condenses into high pressure liquid. The liquid refrigerant flows through the CCV, receiver tank, and drier, into
the liquid lines.
The LLS1 is open so some of the refrigerant flows through the Zone 1 heat exchanger and expansion valve into the evaporator.
There, liquid refrigerant absorbs heat as it evaporates into low pressure vapor. The refrigerant returns to the compressor through
the heat exchanger, SLS1, suction line, SLCV1, accumulator, and ETV.
The LLS2 is also open so some of the refrigerant flows through the Zone 2 heat exchanger and expansion valve into the
evaporator. There, liquid refrigerant absorbs heat as it evaporates into low pressure vapor. The refrigerant returns to the
compressor through the heat exchanger, SLS2, suction line, SLCV2, accumulator, and ETV.
Zone 1 Evaporator
1F. Zone 1 Liquid Line Solenoid (LLS1)-Open/ Energized
2F. Zone 1 Liquid Return Check Valve (LRCV1)-Closed
3F. Zone 1 Suction Line Solenoid (SLS1)-Open/ De-energized
4F. Zone 1 Suction Line Check Valve (SLCV1)-Open
5F. Zone 1 Hot Gas Solenoid (HGS1)-Closed/ De-energized
Zone 2 Evaporator
1R. Zone 2 Liquid Line Solenoid (LLS2)-Open/ Energized
2R. Zone 2 Liquid Return Check Valve (LRCV2)-Closed
3R. Zone 2 Suction Line Solenoid (SLS2)-Open/ De-energized
4R. Zone 2 Suction Line Check Valve (SLCV2)-Open
5R. Zone 2 Hot Gas Solenoid (HGS2)-Closed/ De-energized
Condensing Unit
6. Condenser Inlet Solenoid (CIS)-Open/ De-energized
7. Liquid Injection Solenoid (LIS)-Closed/De-energized but the microprocessor will open it if necessary to control compressor
temperature.
8. Condenser Check Valve (CCV)-Open
9. Receiver Tank Pressure Solenoid (RTPS)-Closed/De-energized
10. Purge Valve (PV)-Closed/De-energized
11. Purge Check Valve (PCV)-Closed
12. Hot Gas Bypass Solenoid (HGBS)-Closed/De-energized but the microprocessor will open it if necessary to control suction
pressure.
Solenoid Delays
HGS Delay – When there is a requirement for the CIS valve to open (de-energize) and a HGS to close (de-energize), the HGS
will delay closing (de-energizing) for 5 seconds.
Summary of Contents for T-1000R
Page 14: ...Safety Precautions 2 6 Warning Decals 2e24151g0 ...
Page 34: ...Maintenance Inspection Schedule 4 10 ...
Page 57: ...Unit Description 5 23 Purge Mode UT Series 1 3 4 5 2 ...
Page 67: ...Unit Description 5 33 Zone 1 Cool and Zone 2 Cool UT SPECTRUM Units ...
Page 69: ...Unit Description 5 35 Purge Mode UT SPECTRUM Units ...
Page 71: ...Unit Description 5 37 Zone 1 Cool and Zone 2 Heat UT SPECTRUM Units ...
Page 72: ...Unit Description 5 38 ...
Page 74: ...Diesel Electric Menu 6 28 Adjust Brightness 6 29 Time 6 30 ...
Page 120: ...Operating Instructions Standard HMI 7 18 ...
Page 152: ...Engine Maintenance 9 14 T Series Fuel and Oil System Components TK 376 ...
Page 154: ...Engine Maintenance 9 16 T Series Fuel and Oil System Components TK 270 ...
Page 156: ...Engine Maintenance 9 18 UT Series Fuel System Components AMA768 ...
Page 172: ...Engine Maintenance 9 34 T Series Engine Mounting Components for 2 Cylinder Engine ...
Page 184: ...Engine Maintenance 9 46 ...
Page 238: ...Refrigeration Maintenance 10 54 ...
Page 246: ...Clutch Maintenance 11 8 ...
Page 258: ...Structural Maintenance 12 12 ...
Page 264: ...Mechanical Diagnosis 13 6 ...
Page 265: ...14 Electric Standby Diagnosis ...
Page 268: ...Electric Standby Diagnosis 14 4 ...
Page 269: ...15 Refrigeration System Diagnosis ...
Page 272: ...Refrigeration System Diagnosis 15 4 ...
Page 280: ...Remote Evaporators 16 8 ...