Operating Instructions Premium HMI
6-12
Prompt Screen, Guarded Access Set to Yes
The display then shows the Defrost display. The bar indicator shows approximately how much time remains to complete the
defrost cycle. The bar indicator in Figure shows that the defrost cycle is about 25% complete.
Defrost Display
Terminating a Defrost Cycle
The defrost cycle terminates automatically when the coil temperature is greater than or equal to 52 F (11 C) or the defrost timer
expires. Defrost can also be terminated by turning the unit off and back on.
SELECTING HIGH SPEED LOCKOUT MODE (IF ENABLED)
High speed operation can be locked out in noise sensitive areas if required.
Note: High Speed Lockout Enable must be set to [Enabled] in the Guarded Access/Programmable Features Menu or this feature will not
be available.
Important: HIGH SPEED LOCKOUT TIMEOUT
(configuration only possible with Service tool):
If High Speed Lockout Mode is selected, the
High Speed Inhibit Timeout feature may be set to return the unit to normal operation after a set time period has expired. This prevents extended operation with
high speed operation locked out. The time period may be from 15 minutes to 2 hours. If the time period is set and is exceeded the unit will return to normal
operation, with high speed operation allowed. If this occurs, the message HIGH SPEED LOCKOUT ACTIVE at the top of the display will disappear. If
necessary to return to High Speed Lockout Mode, press the High Speed Lockout Key again.
The High Speed Lockout Key is a toggle. If high speed is currently allowed, then pressing the High Speed Lockout Key will
disable high speed operation. Pressing the High Speed Lockout Key again will allow high speed operation. To change the setting,
press the High Speed Lockout key as shown in Figure "Premium HMI Control Panel Premium Display" page 6-3.
The display will briefly show [PROGRAMMING HIGH SPEED LOCKOUT - PLEASE WAIT].
PROGRAMMING HIGH SPEED LOCKOUT - PLEASE WAIT
The change is confirmed by briefly displaying [HIGH SPEED LOCKOUT ACTIVE] or [HIGH SPEED LOCKOUT
INACTIVE].
High Speed Lockout Display
The display will then return to the Premium Display. If High Speed Lockout is turned on, the message HIGH SPEED
LOCKOUT ACTIVE will be shown at the top of the display.
Premium Display, High Speed Lockout Active
Pressing the High Speed Lockout key again will turn the feature off.
Summary of Contents for T-1000R
Page 14: ...Safety Precautions 2 6 Warning Decals 2e24151g0 ...
Page 34: ...Maintenance Inspection Schedule 4 10 ...
Page 57: ...Unit Description 5 23 Purge Mode UT Series 1 3 4 5 2 ...
Page 67: ...Unit Description 5 33 Zone 1 Cool and Zone 2 Cool UT SPECTRUM Units ...
Page 69: ...Unit Description 5 35 Purge Mode UT SPECTRUM Units ...
Page 71: ...Unit Description 5 37 Zone 1 Cool and Zone 2 Heat UT SPECTRUM Units ...
Page 72: ...Unit Description 5 38 ...
Page 74: ...Diesel Electric Menu 6 28 Adjust Brightness 6 29 Time 6 30 ...
Page 120: ...Operating Instructions Standard HMI 7 18 ...
Page 152: ...Engine Maintenance 9 14 T Series Fuel and Oil System Components TK 376 ...
Page 154: ...Engine Maintenance 9 16 T Series Fuel and Oil System Components TK 270 ...
Page 156: ...Engine Maintenance 9 18 UT Series Fuel System Components AMA768 ...
Page 172: ...Engine Maintenance 9 34 T Series Engine Mounting Components for 2 Cylinder Engine ...
Page 184: ...Engine Maintenance 9 46 ...
Page 238: ...Refrigeration Maintenance 10 54 ...
Page 246: ...Clutch Maintenance 11 8 ...
Page 258: ...Structural Maintenance 12 12 ...
Page 264: ...Mechanical Diagnosis 13 6 ...
Page 265: ...14 Electric Standby Diagnosis ...
Page 268: ...Electric Standby Diagnosis 14 4 ...
Page 269: ...15 Refrigeration System Diagnosis ...
Page 272: ...Refrigeration System Diagnosis 15 4 ...
Page 280: ...Remote Evaporators 16 8 ...