ULTRA-CUT 200 XT
Manual 0-5304
INSTALLATION
3-1
SECTION 3: INSTALLATION
3.01 Installation Requirements
Electric Supply
The electrical supply network, the gas and water supply system must meet local safety standards. This conformity shall be
checked by qualified personnel.
Ultra-Cut 200 XT™ Power Supply
Input
Power Input
Current
Suggested Sizes (See Note)
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps)
Wire (AWG) Wire (mm
2
)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
3-Ph
480
50/60
42
52
100
#8
10
NOTE!
* Suggested wire size based on United States NFPA 70 National Electrical Code 2011 edition
published by the National Fire Prevention Association. Listings are from table 400.5(A)(2) for
flexible cord of certain types rated for 75 deg C in ambient temperatures up to 30 deg C. Using
wires of lower temperature rating or different insulation type may require larger wire size. De
rate for higher ambient.
These are suggestions only. Always refer to your local and national codes that apply to your
region for final determination of correct wire type and size.
Gas Supply
The customer must supply all gases and pressure regulators. Gases must be of high quality. Pressure regulators must be double-
stage and installed as close as possible to the gas console. Contaminated gas can cause one or more of the following problems:
• Reduced cutting speed
• Poor cut quality
• Poor cutting precision
• Reduced consumables life.
• Oil or grease contamination from compressed or bottled air can cause fires in conjunction with oxygen.
Cooling System Requirements
Coolant must be added to the system on installation. The amount required varies with torch leads length.
Victor Thermal Dynamics recommends the use of its coolants 7-3580 and 7-3581 (for low temperatures).
Coolant Capabilities
Cat. Number and Mixture
Mixture
Protects To
7-3580 ‘Extra-Cool™’
25 / 75
10° F / -12° C
7-3581 ‘Ultra-Cool™’
50 / 50
-27° F / -33° C
7-3582 ‘Extreme Cool™’
Concentrate*
-76° F / -60° C
* For mixing with D-I Cool™ 7-3583
Summary of Contents for ULTRA-CUT 200 XT
Page 6: ...This Page Intentionally Blank...
Page 15: ...ULTRA CUT 200 XT Manual 0 5304 SAFETY INSTRUCTIONS 1 5 This Page Intentionally Blank...
Page 28: ...ULTRA CUT 200 XT SPECIFICATIONS Manual 0 5304 This Page Intentionally Blank...
Page 76: ...ULTRA CUT 200 XT INSTALLATION Manual 0 5304 This Page Intentionally Blank...
Page 160: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 17 Cap Bias Bottom PCB Layout Art A 11685_AB...
Page 162: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 19 Suppressor PCB Layout Art A 11684_AB...
Page 165: ...ULTRA CUT 200 XT Manual 0 5304 APPENDIX A 39 This Page Intentionally Blank...
Page 227: ......