1J-2 Charging System:
Battery Runs Down Quickly
B944H11A04002
Troubleshooting
Battery overcharges
Faulty regulator/rectifier.
Replace.
Faulty battery.
Replace.
Poor contact of generator lead wire
coupler.
Repair.
“Sulfation”, acidic white
powdery substance or
spots on surface of cell
plates
Cracked battery case.
Replace the battery.
Battery has been left in a run-down
condition for a long time.
Replace the battery.
Battery runs down quickly
Trouble in charging system.
Check the generator, regulator/rectifier and
circuit connections and make necessary
adjustments to obtain specified charging
operation.
Cell plates have lost much of their active
materials a result of overcharging.
Replace the battery and correct the charging
system.
Internal short-circuit in the battery.
Replace the battery.
Too low battery voltage.
Recharge the battery fully.
Too old battery.
Replace the battery.
Battery “sulfation”
Incorrect charging rate. (When not in
use battery should be checked at least
once a month to avoid sulfation.)
Replace the battery.
The battery was left unused in a cold
climate for too long.
Replace the battery if badly sulfated.
Condition
Possible cause
Correction / Reference Item
Step
Action
Yes
No
1
Check accessories which use excessive amounts of
electricity.
Are accessories being installed?
Remove accessories.
Go to Step 2.
2
Check the battery for current leakage. Refer to “Battery
Current Leakage Inspection (Page 1J-3)”.
Is the battery for current leakage OK?
Go to Step 3.
• Short circuit of wire
harness.
• Faulty electrical
equipment.
3
Measure the regulated voltage between the battery
terminals. Refer to “Regulated Voltage Inspection (Page 1J-
3)”.
Is the regulated voltage OK?
• Faulty battery.
• Abnormal driving
condition.
Go to Step 4.
4
Measure the resistance of the generator coil. Refer to
“Generator Inspection (Page 1J-4)”.
Is the resistance of generator coil OK?
Go to Step 5.
• Faulty generator coil.
• Disconnected lead
wires.
5
Measure the generator no-load performance. Refer to
“Generator Inspection (Page 1J-4)”.
Is the generator no-load performance OK?
Go to Step 6.
Faulty generator.
6
Inspect the regulator/rectifier. Refer to “Regulator / Rectifier
Inspection (Page 1J-8)”.
Is the regulator/rectifier OK?
Go to Step 7.
Faulty regulator/rectifier.
7
Inspect wiring harness.
Is the wiring harness OK?
Faulty battery.
• Short circuit of wire
harness.
• Poor contact of
couplers.
Summary of Contents for SFV650
Page 1: ...SFV650 SERVICE MANUAL 9 9 5 0 0 3 6 1 9 0 0 1 E...
Page 4: ......
Page 283: ...Engine Lubrication System 1E 4 REAR CYLINDER I944H1150043 02...
Page 420: ...2D 20 Wheels and Tires...
Page 434: ...3A 12 Drive Chain Drive Train Drive Shaft...
Page 472: ...4C 10 Rear Brakes...
Page 572: ...Prepared by December 2008 Part No 99500 36190 01E Printed in Japan 572...
Page 573: ...Printed in Japan K9...