situation alarm is shown on display and digital output (general
alarm) is enabled.
Condensation pressure probe fault (only LN version):
is fault (short circuit or interruption) control waits a time since event
(10 sec) after switches off all analogic and digital outputs of the
devices: compressor, heater (if present), evaporator fan and
condenser fan. In this situation alarm is shown on display and digital
output (general alarm) is enabled.
Intake high temperature (only three phase models, except
CV(E/O)60-CV(E/O)4000): allarm is ON after time Exclusion alarm
power cp (30 sec) from switching on of the compressor and if the
temperature of the probe Suction temperature is
suction temperature. In this case there is a uncorrect temperature
on the suction tube of the compressor. If the alarm is present, it
switch off digital ind analogic outputs of the devices. In this situation
alarm is shown on display and digital output (gene
enabled. In case alarm is present check correct sequence of the
phases. The reset of the alarm is manual, it is necessary to press key
Down for 3 seconds and if the Suction temperature will have to
Set point alarm suction temperature - Hysteresis alarm suction
temperature (condition in according to ambient temperature too).

LABEL MEANING

MODE

P1

alarm probe B1

flashing

P4

alarm probe B4

alternation to temp.

HA

alarm high temperature B1

alternation to temp.

LA

alarm low temperature B1

alternation to temp.

HP

alarm high pressure

alternation to temp.

SEC

alarm sequence

alternation to temp.

HAS

alarm sunction temperature

alternation to temp

Check unit mode

Check unit mode is attivable only when controller is on state ON, to
enter on check unit mode press key DOWN + ON/OFF at least 5
seconds. Procedure will start, sequence of step is enable pressing
key UP, with key DOWN come back previous step.
On check unit mode it is necessary to consider safety alarms from
device, in detail: hige pressure switch and sequence phase alarm,
intake.

Step 1:

-

Activation evaporator fan is on “Fan always ON”

-

Display flashing message “FAn”, it means that evaporator fan is

forced on

Step 2:

-

No function. Skip to step 3

Step 3:

-

Activation compressor and condenser fan by

time switch off compressor, minium time between two start of
compressor.

-

Display flashing message “CPr”, it means that unit is forced on

cooling mode

Step 4:

-

Disactivation compressor by-passing minimum time switch off

compressor, minium time between two start of compressor.
-

Disactivation condenser fan

-

Activation heater

-

Display flashing message “Htr”, it means that heater is forced

on

26

situation alarm is shown on display and digital output (general

(only LN version): in case probe

is fault (short circuit or interruption) control waits a time since event

off all analogic and digital outputs of the

heater (if present), evaporator fan and

condenser fan. In this situation alarm is shown on display and digital

Intake high temperature (only three phase models, except

allarm is ON after time Exclusion alarm

power cp (30 sec) from switching on of the compressor and if the
temperature of the probe Suction temperature is

≥ Set point alarm 

ction temperature. In this case there is a uncorrect temperature

on the suction tube of the compressor. If the alarm is present, it
switch off digital ind analogic outputs of the devices. In this situation
alarm is shown on display and digital output (general alarm) is
enabled. In case alarm is present check correct sequence of the
phases. The reset of the alarm is manual, it is necessary to press key
Down for 3 seconds and if the Suction temperature will have to

≤ 

eresis alarm suction

temperature (condition in according to ambient temperature too).

MODE

flashing
alternation to temp.
alternation to temp.
alternation to temp.
alternation to temp.
alternation to temp.
alternation to temp

Check unit mode is attivable only when controller is on state ON, to

check unit mode press key DOWN + ON/OFF at least 5

seconds. Procedure will start, sequence of step is enable pressing
key UP, with key DOWN come back previous step.
On check unit mode it is necessary to consider safety alarms from

pressure switch and sequence phase alarm,

Activation evaporator fan is on “Fan always ON”
Display flashing message “FAn”, it means that evaporator fan is

condenser fan by-passing minimum

time switch off compressor, minium time between two start of

Display flashing message “CPr”, it means that unit is forced on

passing minimum time switch off

essor, minium time between two start of compressor.

Display flashing message “Htr”, it means that heater is forced

Step 5:

-

Exit check unit mode and return to normal functioning

If time of a step is ≥ a 30 

min or controller is reactivated, unit exit

automatically from check unit mode.

Signal type

GENERAL ALARM: when there is an alarm it is shown on display and
corresponding digital output changes state. 1 pole type, change
over contact (max 8A resistivity e 2A inductive, 250Vac). Alarm
occurs also in case of power supply is missing.
REMOTE ENABLE: contact NC, voltage f
“Stb”.

8. INSTALLATION

ATTENTION!

Unit has to be installed in according national standard of state that

it sold

ATTENTION!

The unit must be handled using the appropriate lifting devices

inserting the eyebolts (M6/M8

General indication before installation

Make sure following points before installation:
-

installation site must not be excessively dirty and moist

ATTENTION

In case the ambient is particularly wet, condensate water can

create on compressor and it can come out from holes on the base

-

cabinet on which the air conditioner has to be installed has a

IP54, or higher, protection degree
-

make sure that available voltage is correct

-

the interior of the cabinet is clean

-

holes, screws, wires do not interface with the equipment

already installed
-

air conditioner will work on vertical position (laid perfectly)

Choosing of installation place

-

cabinet is not located near to heat sources or hot air flows

-

if it installed on the door, make sure that the hinges can support

the weight of the unit
-

if the depth of the exchanger prevents the door from opening

fully, fit a door stop
-

make sure that there is enough space both internally and

externally
-

the internal of the cabinet allows a correct circulation of air,

avoiding recirculation
-

make sure that the supply and intake air openings are free and

there is at least a distance of 200mm from walls or construction
elements
-

make sure that it is possible to carry out a correct system of

discharge

of

condensate

CVE-CVO

Exit check unit mode and return to normal functioning

min or controller is reactivated, unit exit

automatically from check unit mode.

GENERAL ALARM: when there is an alarm it is shown on display and
corresponding digital output changes state. 1 pole type, change

e 2A inductive, 250Vac). Alarm

occurs also in case of power supply is missing.
REMOTE ENABLE: contact NC, voltage free signal. Shown message

ATTENTION!

Unit has to be installed in according national standard of state that

it sold

ATTENTION!

The unit must be handled using the appropriate lifting devices

M6/M8) in the prearranged holes.

General indication before installation

Make sure following points before installation:

installation site must not be excessively dirty and moist

ATTENTION!

In case the ambient is particularly wet, condensate water can

create on compressor and it can come out from holes on the base

cabinet on which the air conditioner has to be installed has a

make sure that available voltage is correct
the interior of the cabinet is clean
holes, screws, wires do not interface with the equipment

air conditioner will work on vertical position (laid perfectly)

cabinet is not located near to heat sources or hot air flows
if it installed on the door, make sure that the hinges can support

epth of the exchanger prevents the door from opening

make sure that there is enough space both internally and

the internal of the cabinet allows a correct circulation of air,

ly and intake air openings are free and

there is at least a distance of 200mm from walls or construction

make sure that it is possible to carry out a correct system of

discharge

of

condensate

Summary of Contents for Cosmotec CVE Series

Page 1: ...D WARTUNGSHANDBUCH MANUEL D UTILISATION ET D ENTRETIEN MANUAL DE USO Y MANTENIMIENTO CVE CVO Condizionatore per armadi elettrici Air conditioner for electric enclosure Klimager t f r Elektroschaltschr...

Page 2: ......

Page 3: ...CVE CVO 3...

Page 4: ...CVE CVO 4...

Page 5: ...installatori o utilizzatori del prodotto per migliorare il contenuto del presente manuale sono particolarmente gradite dal costruttore SIMBOLI USATI NEL MANUALE PERICOLO RISCHIO DI LESIONI PER L OPER...

Page 6: ...entamente l apparecchiatura prima dell accensione ed eventualmente Non far funzionare resa franco fabbrica Tutte le unit sono state singolarmente controllate in ogni loro parte e attentamente imballat...

Page 7: ...re una perfetta tenuta GAS FRIGORIGENO R134a Tetrafluoroetano Non ne tossico ne infiammabile e non dannoso per lo strato d ozono COMPRESSORE E di tipo alternativo rotativo o scroll CONDENSATORE E il c...

Page 8: ...E se presente Nei modelli di grossa potenza viene utilizzato per la trasformazione della tensione di rete a quella degli ausiliari AUTOTRASFORMATORE se presente E presente nei modelli funzionanti con...

Page 9: ...ed per indicare che la sonda non abilitata B2 B3 no Relativamente alla sonda B4 potr essere visualizzato un valore di pressione espresso in bar o PSI la label Err lampeggiante per indicare che la sond...

Page 10: ...a tastiera in questo caso il ventilatore si ferma trascorso il tempo di ritardo allo spegnimento e solamente se il compressore fermo allarmi che ne prevedano lo spegnimento in questo caso il tempo di...

Page 11: ...logiche relative ai dispositivi compressore resistenza di riscaldamento ventilatore evaporatore ventilatore condensatore In questa condizione si visulizza l allarme sul display e si attiva l uscita di...

Page 12: ...apparecchiature gi re funzioner in posizione verticale l armadio non sia in prossimit di fonti di calore o flussi d aria se installato su porta assicurasi che le cerniere sostengano il la profondit d...

Page 13: ...a personale specializzato ed autorizzato ATTENZIONE Prima di effettuare qualsiasi intervento sull unit togliere l alimentazione elettrica ATTENZIONE Prima di effettuare qualsiasi allacciamento indispe...

Page 14: ...sono necessari pi Agganciare il filtro tramite le due linguette poste nella parte inferiore alla griglia di aspirazione del pannello Posizionare il filtro ite siano appoggiate Il filtro deve essere po...

Page 15: ...Controllo e logica di funzionamento Evitare fermate e immediate ripartenza del compressore Tra la fermata e la successiva ripartenza devono trascorrere almeno 3 minuti Modalit di collaudo possibile ef...

Page 16: ...unit priva di tensione a terra con liquido detergente ed aria compressa con pressione superiore a 4 bar SOSTE DI INATTIVITA Se l unit rimane per lungo tempo inattiva necessario scaricare eventuali res...

Page 17: ...mentazione all apparecchiatura prima di rilevare i valori di resistenza Verificare che nei circuiti di bassa tensione non sia presente usare utensili magnetici in prossimit di forti campi 11 3 6 NORME...

Page 18: ...to avendo cura di separare i seguenti materiali Refrigerante I refrigeranti utilizzati non sono nocivi per l ozono stratosferico ma contribuiscono ad aggravare il riscaldamento globale E quindi obblig...

Page 19: ...taforesi Versione LN regolatore di velocit ventilatore condensatore Controlla la velocit del ventilatore condensatore in modo da ridurre la rumorosit La velocit del ventilatore viene regolata attraver...

Page 20: ...CEDURE INFORMATION IMPORTANT INFORMATION CHANGE OF OWNERSHIP Inform STULZ SpA of the address of the new owner in order to allow any supplements to the manual to be sent Otherwise will not be held resp...

Page 21: ...it indicative of a leak of coolant inside or outside inspect the equipment carefully before switching technical department Do not operate the unit if there is a leak of coolant free ex works All the u...

Page 22: ...corrosion resistance The structure can be easily inspected and at the same time provides adequate protection for the internal components On unit CVE there are two lateral aluminium frame The componen...

Page 23: ...ansform from mains voltage to auxiliaries voltage AUTOTRANSFORMER if present It is present in models that they work with voltage bi phase 230V and three phase They are manufactured according to standa...

Page 24: ...nit from ON to OFF and e vice versa Relay of alarm remains on normal working state STAND BY state STAND BY is connected to digital input Remote Enable In case contact is open controller doens t make n...

Page 25: ...ion parameters Default value range SEt Set point 35 25 25 45 Main unit no ot Max time activation unit 0 SH Differential for unit on stand by 5 Label Description parameters Default value range HY Hyste...

Page 26: ...ep is enable pressing key UP with key DOWN come back previous step On check unit mode it is necessary to consider safety alarms from pressure switch and sequence phase alarm Activation evaporator fan...

Page 27: ...f condens condenser fan and fix the condenser fan plate Re connect the cable of display and fix the panel Note to make easy the positioning of air conditioner there are 2 male threaded pin and 2 nuts...

Page 28: ...it Figura 3 The nominal voltage is indicated on identification label and technical 48VDC 36 59DC For 50 60Hz two fase 400V 50Hz 60Hz Unit with three phase are produced on factory for power supply 460V...

Page 29: ...necessary to place air probe in a zone where there is air circulation and to avoid the air conditioner intakes air with lower temperature than minimin limit temperature showed in technical label NON C...

Page 30: ...ent are clean and that any dirt does not Check for the presence of unusual noises during operation Check the condensate drain pipe of the unit is fully operating and components do not generate abnorma...

Page 31: ...city Make sure that the condensers connected to the deactivated electrical circuit are discharged Remove the fuses only after the circuit has been deactivated 11 3 5 SAFETY STANDARDS TO RESPECT WHEN C...

Page 32: ...If the compressor oil needs to be replaced it must be disposed The air filters should be disposed of depending on the substances they contain from the environment in which the The gas filters must be...

Page 33: ...unit ATTENTION Cooling capacity could be lower than value on identification plate of the un Electrical heating This option is useful when heating of the internal air is required The electrical reheat...

Page 34: ...isierung der Produktion und der bereits ver ffentlichten Handb cher zu aktualisieren Eventuelle Aktualisierungen des Bedienungshandbuchs oder Erg nzungen die als fester Bestandteil des Handbuchs zu be...

Page 35: ...e befragen Das Ger t nicht in Betrieb setzen falls man einen Austritt des K hlmittels feststellt versendet Alle Teile der Ger te werden einzeln kontrolliert und sorgf ltig verpackt Nach Erhalt ist das...

Page 36: ...ltekreislauf in dem das K hlmittel zirkuliert Das System funktioniert folgenderma en Der Kompressor CO verdichtet das K ltemittel und bringt es auf Hochdruck und Temperatur W hrend das warme Gas durc...

Page 37: ...TEMPERATURSONDE Eine Temperatursonde des Typs NTC ist an der Analogeinheit des elektronischen Controllers angeschlossen HOCHDRUCK SICHERHEITSDRUCKW CHTER Stoppt den Kompressorbetrieb wenn der Druck im...

Page 38: ...lang gedr ckt halten bis die blinkende Aufschrift POF erscheint Jetzt ist die Tastatur gesperrt und es k nnen nur der Sollwert die H chst und Mindesttemperatur angezeigt werden Um die Tastatur zu ent...

Page 39: ...Remote enable angeschlossen ist Maschinenstatus OFF ber Tastatur in diesem Fall schaltet sich das Gebl se nach Ablauf der Abschaltverz gerungszeit aus und nur wenn der Kompressor ausgeschaltet ist Al...

Page 40: ...Ausf hrungen f r den Fall dass der hiermit verbundene Kontakt ge ffnet wird muss der Controller den Kompressor und das Kondensatorgebl se deaktivieren Bei Vorliegen dieser Betriebsbedingung wird der...

Page 41: ...s HAUPTALARM Wenn ein Alarm ausgel st wird wird auf Display die entsprechende Meldung angezeigt und der Digitalausgang wechselt polig mit Umschaltkontakt max 8A Induktivit t 250 Vac Alarm auftritt auc...

Page 42: ...entfernten vorderen Teil wieder einsetzen und befestigen Die zuvor entfernte Gebl seplattewiedereinsetzen und befestigen den Das Frontpaneel wieder befestigen hierzu die Displaykabel Hinweis Um die Au...

Page 43: ...eschlossen f r die Versorgung der Einheiten mit 400V 50Hz ist auf die entsprechenden elektrischen Schaltpl ne Bezug zu nehmen Die angegebenen Nennspannungen haben eineToleranzvon 10 frequenztoleranz 2...

Page 44: ...latte wieder einsetzen das andere Kabelende an den Schl das Benutzersystem an die Parameter und anschlie en das Verfahren aus Kapitel 7 durchf hren um die Modbus Parameter zu ndern Installation der Fe...

Page 45: ...der Aufnahmetemperatur ist der s dreht sich Kompressor in die falsche Richtung und die Kontrollieren dass keine Alarme vorhanden sind Kontrollieren dass die Gebl se richtig funktionieren Kontrollieren...

Page 46: ...pr fen 11 3 GEFAHREN AUFGRUND VON ELEKTRISCHEN ST RUNGEN 11 3 1 SICHERHEITSVORSCHRIFTEN F R ELEKTRISCHE GER TE Einf hrung Die Ursachen von elektrischen Gefahren sind bekannt diese Gefahren k nnen durc...

Page 47: ...Ger t in nicht ausreichend gel fteten oder gro en R umen installiert wird und man merkt dass schnell K hlmittel austritt sollte sich das Personal entfernen und der Raum gel ftet Nicht angemessene Bef...

Page 48: ...der Verdampferventilator funktionieren der Kompressor funktioniert unregelm ig a Eingriff des Hochdruckw chters falls vorhanden Raumtemperatur ber dem maximal zugelassenen Wert siehe Typenschild Den...

Page 49: ...st eine Oberfl chenbehandlung mit Epoxybeschichtung Kondensatoren dagegen ist eine Beschichtung derOberfl chenerforderlich Ausf hrung Geschwindigkeitsregler Kondensatorgebl se SteuertdieGeschwindigkei...

Page 50: ...production et les manuels pr c dents sauf dans les cas exceptionnels Pour demander ou recevoir d ventuelles mises jour ou ajouts apport s au manuel d utilisation qui devront tre consid r s comme part...

Page 51: ...all es avec soin Contr lez imm diatement l unit d s que vous la recevez rifier qu elle a t transport e dans la bonne le sur le document de Nous vous conseillons d accepter la marchandise sous V rifiez...

Page 52: ...ompresseur CO comprime le gaz frigorig ne en l amenant une pression et temp rature lev es le gaz chaud en traversant le condensateur BC est refroidi et liqu fi en c dant de la chaleur l air ambiant Po...

Page 53: ...lateur condensateur lorsque la pression est inf rieure 8 5 bars il permet le fonctionnement du climatiseur une temp rature ambiante allant jusqu 20 C TRANSDUCTEUR DE PRESSION si pr sent Le transducteu...

Page 54: ...is es dans les diff rents r glages La liste des ressources est la suivante valeur sonde B1 valeur sonde B2 valeur sonde B3 valeur sonde B4 valeur sortie analogique AO1 valeur sortie analogique AO2 Uti...

Page 55: ...is il est n cessaire que le compresseur soit teint Smart Energy Management SEM Le ventilateur entre en mode SEM lorsque la temp rature est inf rieure ou gale au point de consigne de refroidissement de...

Page 56: ...tact qui lui est connect le contr leur d sactive le compresseur la r sistance chauffante si pr sente le ventilateur vaporateur et le ventilateur condensateur Dans cette condition on visualise l alarme...

Page 57: ...se former sur le compresseur et ressortir par les trous pr sents sur la que l armoire lectrique o l on veut appliquer le climatiseur ait un indice de protection IP54 ou plus que la tension disponible...

Page 58: ...u climatiseur deux tiges filet es males et deux crous ont t pr vues et doivent tre plac es dans les deux inserts sup rieurs du ch ssis en plus des vis standard afin de pouvoir accrocher le climatiseur...

Page 59: ...est indiqu e sur l tiquette situ e sur l unit et techniques au chapitre 15 Les tensions d alimentation peuvent tre 48VDC 36 59DC Pour les unit s pour les unit s pour les unit s triphas es Les unit s t...

Page 60: ...et faire passer la sonde par le trou r alis pr c demment dans la appliquer la proc dure de modification des param tres SEM2 ATTENTION N cessaire placer la sonde dans une zone concern e par la recircul...

Page 61: ...la garantie Afin de maintenir l efficacit et la s curit de l appareil les dessous devront effectu es tout au long de la intervention sur l unit veuillez couper l alimentation V rifier que l changeur...

Page 62: ...able doit insister sur l utilisation des mesures de s curit sans tol rer ni accepter d carts car cela peut provoquer des dommages aux personnes et aux appareils 11 3 3 HAUTE TENSION Tout contact avec...

Page 63: ...c s durant les op rations d entretien ordinaire ou Afin d effectuer les activit s d limination de fa on correcte et s re l op rateur doit se doter des EPI n cessaires qui sont gants anti coupure gants...

Page 64: ...onne le ventilateur ext rieur ne fonctionne pas le compresseur fonctionne par intermittence a Condensateur lectrique du ventilateur en panne Remplacez le condensateur lectrique b Ventilateur ext rieur...

Page 65: ...os de l unit pour afficher les informations concernant les conditions de travail Pour plus d informations se r f rer au chapitre Contr le et logique de fonctionnement Accessoire uniquement pour unit s...

Page 66: ...constructor aprecia mucho los avisos o propuestas sugeridos por instaladores o usuarios del producto para mejorar el contenido del presente manual S MBOLOS UTILIZADOS EN ESTE MANUAL PELIGRO RIESGO DE...

Page 67: ...ga franco f brica han sido individualmente controladas en todas sus Controle inmediatamente la pieza que acabe de recibir prestando atenci n al hecho de que se haya transportado en una posici n adecua...

Page 68: ...que se enfr a de dicha manera ESTRUCTURA Realizada con paneles autoportantes para garantizar una buena resistencia a la corrosi n se inspecciona f cilmente y garantiza al mismo tiempo una protecci n a...

Page 69: ...se utiliza para la transformaci n de la tensi nde redaaquellade losauxiliares AUTOTRANSFORMADOR si lo hubiera Se encuentra en los modelos que funcionan con tensi n bif sica 230 V y con tensi n trif s...

Page 70: ...SET En lo que concierne a las sondas B1 B2 B3 se podr visualizar un valor de temperatura expresado en grados Celsius o Fahrenheit El t rmino Err intermitente indica que la sonda presenta un error y el...

Page 71: ...los casos siguientes apertura del contacto conectado a la entrada digital Remote enable estado OFF de la m quina desde el teclado en este caso el ventilador se detiene al transcurrir el tiempo de ret...

Page 72: ...caso de aver a de la sonda cortocircuito o interrupci n el control espera un tiempo determinado desde el evento 10 segundos aproximadamente y luego desactiva todas las salidas digitales y anal gicas...

Page 73: ...esor que puede salir de los orificios presentes en la Que el armario el ctrico donde se desea instalar el intercambiador tenga un grado de protecci n IP54 o superior Que los orificios tornillos cables...

Page 74: ...montaje del intercambiador puntos b c ATENCI N No obstruya la circulaci n del aire aspirado o y expulsado del intercambiador Descarga de la condensaci n El tubo de descarga de la condensaci n debe est...

Page 75: ...ci n del intercambiador una protecci n magnetot rmica con curva en clase idad del instalador conforme a la EN 60335 1 60335 Para la elecci n del tipo de protecci n precedente al acondicionador UL haga...

Page 76: ...o minuciosamente antes de la puesta en funcionamiento de la unidad y si es necesario se debe contactar con el Servicio de Asistencia al Cliente de STULZ ATENCI N LateclaON OFF de lapantallaseusasolame...

Page 77: ...s unidades que contienen m s de 3 kg de refrigerante es obligado comprobar la ausencia de p rdidas de refrigerante seg n el Reglamento Europeo 842 2006 Los controles deben anotarse en el registro de l...

Page 78: ...DISPOSITIVO EST APAGADO Quite la alimentaci n de la unidad antes de intervenir Aseg rese de que despu s no haya tensi n en los circuitos Limpie y seque la zona de trabajo Quitar clavijas anillos estri...

Page 79: ...orio consultar al personal de referencia de la zona antes de empezar los trabajos La eliminaci n del embalaje de la unidad debe efectuarse Los embalajes de madera no est n tratados qu micamente a no s...

Page 80: ...TULZ SpA 3 El compresor y el ventilador externo funcionan el ventilador interno no funciona a El condensador el ctrico del ventilador no funciona Sustituya el condensador el ctrico del ventilador b Ve...

Page 81: ...uerto serial para MODBUS Puerto serial para la conexi n a un sistema de motorizaci n por medio del protocolo de comunicaci n Modbus RTU Sonda remota para la funci n SEM2 Sonda de sustituci n de la sum...

Page 82: ...CVE CVO 82 15 DATI TECNICI TECHNICAL DATA TECHNISCHE DATEN DONNEES TECHNIQUES DATOS T CNICOS Dati 230V UL a 60Hz data 230V UL at 60Hz daten 230V UL zu 60Hz donnees 230V UL 60Hz datos 230V UL en 60Hz...

Page 83: ...CVE CVO 83...

Page 84: ...CVE CVO 84...

Page 85: ...uissance sonore mesur selon la norme ISO 9614 2 avec des conditions normales d utilisation et dans des conditions de fonctionnement conformes Schalldruckpegel auf dem externen Kreislauf bezogen Aufgru...

Page 86: ...rd F r die CE Ausf hrung wird das Modell CVE CVO 05 08 als Beispiel gezeigt F r die UL Einheiten hingegen die Dichtung wie in der Abbildung dargestellt anbringen Hinweis A In der Abbildung wird der An...

Page 87: ...CVE CVO 87 CVE03 UL CVE 05 08 UL CVO 05 08 UL CVE 11 15 UL CVO 11 15 UL CVE20 UL CVO20 UL CVE 30 40 UL CVO 30 40 UL CVE60 UL CVO60 UL A A A B B B B B B B B...

Page 88: ......

Reviews: