background image

CVE-CVO

31

Supervisors must be in constant contact with those in control

Transit areas, stairs and doorways located near to the

equipment must not be obstructed.

Emergency exits must never be obstructed.

Slippery areas that constitute a potential risk to personnel must

be covered with a non-slip material.

Specific tools and procedures must be adopted for each specific

activity.

Test equipment and tools must be maintained in good working

order.

Personnel must have a detailed knowledge of the methods and

procedures adopted in the case of fire (place extinguishers within
easy reach)

11.2 HAZARDS DERIVING FROM CONTACT BETWEEN THE PRODUCT
AND PERSONS OR OBJECTS.

Hazard created by fan movement. The fan guard prevents the

passage of solid objects of dimensions exceeding 8mm

Danger due to possible accidental contact with the heat

exchanger whose aluminium fins may have sharp edges.

Do not pass any objects through the fan guard to check whether

the fan is operating

11.3 HAZARDS DERIVING FROM ELECTRICAL PROBLEMS

11.3.1 SAFETY STANDARDS FOR ELECTRICAL EQUIPMENT
Introduction

The causes of electrical hazards are well known, while their
prevention is not difficult providing constant attention is paid. In
order to reduce these hazards, personnel working with electricity
must be informed and instructed on the appropriate safety
procedures.

11.3.2 MANAGEMENT RESPONSIBILITIES

Managers must be informed of the potential hazards that exist in
the system and must supervise the personnel working on the
electrical equipment. This supervision activity consists of identifying
possible hazardous conditions and investigating the problems
encountered by personnel during maintenance operations. Each
defective component must be repaired or replaced immediately.
The manager must insist on the adoption of safety measures
without tolerating or accepting any deviations, otherwise damage
and or injury could result.

11.3.3 HIGH VOLTAGE

Contact with circuits through which high voltages pass can cause
burns, shock, unconsciousness and could even lead to death by
electrocution. This could be due to insufficient knowledge of the
dangers linked to electrical equipment. The damage caused to the
human body depends on the amount of current, its duration and
path taken by it through the human organism.

11.3.4 SAFETY STANDARDS TO RESPECT WHEN THE EQUIPMENT IS
SWITCHED OFF.

Disconnect the unit from the power supply before undertaking

any work

However make sure that there is no voltage in the circuits.

Clean and dry the working area.

Remove any pins, rings, straps or any other metal objects that

may interfere with the work or become potential conductors of
electricity.

Make sure that the condensers connected to the deactivated

electrical circuit are discharged.

Remove the fuses only after the circuit has been deactivated.

11.3.5 SAFETY STANDARDS TO RESPECT WHEN CARRYING OUT
MAINTENANCE ON LIVE EQUIPMENT

In addition to that described in item 2.3.4, the following
requirements must also be complied with:

Personnel must not work alone.

If possible, use one hand only to carry out the work.

Periodically check the instruments and the conductor wires.

Only follow authorised procedures when bypassing interlocks.

Make sure that the personnel assigned to do the work are

perfectly aware of the component parts of the equipment and the
maintenance procedures before starting any operations.

Wear a pair of insulated gloves.

Open all the contacts that feed power to the equipment before

measuring any resistance values.

Make sure that there is no high voltage present in low voltage

circuits.

Do not use magnetic tools near to strong magnetic fields.

11.3.6 SAFETY STANDARDS TO RESPECT DURING MAINTENANCE
WORK

If continuous operation is not required, the system must always be
switched off.
Before carrying out any maintenance work:

The maintenance technician must not be wearing any objects

that could act as conductors of electricity

The working area must be inspected and it must be ensured

that the floor is dry and clean

The working tools must be checked: in order to carry out the

work in safety, these must be suitable for the purpose and in good
condition

Measuring instruments must be periodically calibrated

The working procedures must be checked prior to starting any

operations, referring to the wiring diagrams and taking note of how
the system is structured.

While performing electrical maintenance work:

The technician must be aware of circuits carrying high voltages

Resistance measurements must not be carried out on live

circuits

Only one hand must be used for measuring live circuits

The instrument terminals must be grounded prior to measuring

live circuits

The above suggestions must be followed carefully

Maintenance works are only deemed completed once all the
components have been reinstalled and the equipment is returned to
its normal condition.

11.4 FIRE HAZARDS

No direct danger of fire. Coolant gas in the presence of flame
develops toxic and corrosive substances. Refer to safety data sheet
of gas. Given the relatively low amount of gas contained in the air
conditioner, the risk prevention is to place the unit in sufficiently
ventilated rooms.

11.5 TOXIC SUBSTANCES

The gas in this unit is environmentally friendly and it is called R134a
(Tetrafluoroethane). It is of reduced amount and the circuit is
completely sealed. During the tests all leaks greater than 3 grams
per year are checked and removed. The coolant gas manufacturer
declares that gas concentrations less than 1/1000 are harmless. If

Summary of Contents for Cosmotec CVE Series

Page 1: ...D WARTUNGSHANDBUCH MANUEL D UTILISATION ET D ENTRETIEN MANUAL DE USO Y MANTENIMIENTO CVE CVO Condizionatore per armadi elettrici Air conditioner for electric enclosure Klimager t f r Elektroschaltschr...

Page 2: ......

Page 3: ...CVE CVO 3...

Page 4: ...CVE CVO 4...

Page 5: ...installatori o utilizzatori del prodotto per migliorare il contenuto del presente manuale sono particolarmente gradite dal costruttore SIMBOLI USATI NEL MANUALE PERICOLO RISCHIO DI LESIONI PER L OPER...

Page 6: ...entamente l apparecchiatura prima dell accensione ed eventualmente Non far funzionare resa franco fabbrica Tutte le unit sono state singolarmente controllate in ogni loro parte e attentamente imballat...

Page 7: ...re una perfetta tenuta GAS FRIGORIGENO R134a Tetrafluoroetano Non ne tossico ne infiammabile e non dannoso per lo strato d ozono COMPRESSORE E di tipo alternativo rotativo o scroll CONDENSATORE E il c...

Page 8: ...E se presente Nei modelli di grossa potenza viene utilizzato per la trasformazione della tensione di rete a quella degli ausiliari AUTOTRASFORMATORE se presente E presente nei modelli funzionanti con...

Page 9: ...ed per indicare che la sonda non abilitata B2 B3 no Relativamente alla sonda B4 potr essere visualizzato un valore di pressione espresso in bar o PSI la label Err lampeggiante per indicare che la sond...

Page 10: ...a tastiera in questo caso il ventilatore si ferma trascorso il tempo di ritardo allo spegnimento e solamente se il compressore fermo allarmi che ne prevedano lo spegnimento in questo caso il tempo di...

Page 11: ...logiche relative ai dispositivi compressore resistenza di riscaldamento ventilatore evaporatore ventilatore condensatore In questa condizione si visulizza l allarme sul display e si attiva l uscita di...

Page 12: ...apparecchiature gi re funzioner in posizione verticale l armadio non sia in prossimit di fonti di calore o flussi d aria se installato su porta assicurasi che le cerniere sostengano il la profondit d...

Page 13: ...a personale specializzato ed autorizzato ATTENZIONE Prima di effettuare qualsiasi intervento sull unit togliere l alimentazione elettrica ATTENZIONE Prima di effettuare qualsiasi allacciamento indispe...

Page 14: ...sono necessari pi Agganciare il filtro tramite le due linguette poste nella parte inferiore alla griglia di aspirazione del pannello Posizionare il filtro ite siano appoggiate Il filtro deve essere po...

Page 15: ...Controllo e logica di funzionamento Evitare fermate e immediate ripartenza del compressore Tra la fermata e la successiva ripartenza devono trascorrere almeno 3 minuti Modalit di collaudo possibile ef...

Page 16: ...unit priva di tensione a terra con liquido detergente ed aria compressa con pressione superiore a 4 bar SOSTE DI INATTIVITA Se l unit rimane per lungo tempo inattiva necessario scaricare eventuali res...

Page 17: ...mentazione all apparecchiatura prima di rilevare i valori di resistenza Verificare che nei circuiti di bassa tensione non sia presente usare utensili magnetici in prossimit di forti campi 11 3 6 NORME...

Page 18: ...to avendo cura di separare i seguenti materiali Refrigerante I refrigeranti utilizzati non sono nocivi per l ozono stratosferico ma contribuiscono ad aggravare il riscaldamento globale E quindi obblig...

Page 19: ...taforesi Versione LN regolatore di velocit ventilatore condensatore Controlla la velocit del ventilatore condensatore in modo da ridurre la rumorosit La velocit del ventilatore viene regolata attraver...

Page 20: ...CEDURE INFORMATION IMPORTANT INFORMATION CHANGE OF OWNERSHIP Inform STULZ SpA of the address of the new owner in order to allow any supplements to the manual to be sent Otherwise will not be held resp...

Page 21: ...it indicative of a leak of coolant inside or outside inspect the equipment carefully before switching technical department Do not operate the unit if there is a leak of coolant free ex works All the u...

Page 22: ...corrosion resistance The structure can be easily inspected and at the same time provides adequate protection for the internal components On unit CVE there are two lateral aluminium frame The componen...

Page 23: ...ansform from mains voltage to auxiliaries voltage AUTOTRANSFORMER if present It is present in models that they work with voltage bi phase 230V and three phase They are manufactured according to standa...

Page 24: ...nit from ON to OFF and e vice versa Relay of alarm remains on normal working state STAND BY state STAND BY is connected to digital input Remote Enable In case contact is open controller doens t make n...

Page 25: ...ion parameters Default value range SEt Set point 35 25 25 45 Main unit no ot Max time activation unit 0 SH Differential for unit on stand by 5 Label Description parameters Default value range HY Hyste...

Page 26: ...ep is enable pressing key UP with key DOWN come back previous step On check unit mode it is necessary to consider safety alarms from pressure switch and sequence phase alarm Activation evaporator fan...

Page 27: ...f condens condenser fan and fix the condenser fan plate Re connect the cable of display and fix the panel Note to make easy the positioning of air conditioner there are 2 male threaded pin and 2 nuts...

Page 28: ...it Figura 3 The nominal voltage is indicated on identification label and technical 48VDC 36 59DC For 50 60Hz two fase 400V 50Hz 60Hz Unit with three phase are produced on factory for power supply 460V...

Page 29: ...necessary to place air probe in a zone where there is air circulation and to avoid the air conditioner intakes air with lower temperature than minimin limit temperature showed in technical label NON C...

Page 30: ...ent are clean and that any dirt does not Check for the presence of unusual noises during operation Check the condensate drain pipe of the unit is fully operating and components do not generate abnorma...

Page 31: ...city Make sure that the condensers connected to the deactivated electrical circuit are discharged Remove the fuses only after the circuit has been deactivated 11 3 5 SAFETY STANDARDS TO RESPECT WHEN C...

Page 32: ...If the compressor oil needs to be replaced it must be disposed The air filters should be disposed of depending on the substances they contain from the environment in which the The gas filters must be...

Page 33: ...unit ATTENTION Cooling capacity could be lower than value on identification plate of the un Electrical heating This option is useful when heating of the internal air is required The electrical reheat...

Page 34: ...isierung der Produktion und der bereits ver ffentlichten Handb cher zu aktualisieren Eventuelle Aktualisierungen des Bedienungshandbuchs oder Erg nzungen die als fester Bestandteil des Handbuchs zu be...

Page 35: ...e befragen Das Ger t nicht in Betrieb setzen falls man einen Austritt des K hlmittels feststellt versendet Alle Teile der Ger te werden einzeln kontrolliert und sorgf ltig verpackt Nach Erhalt ist das...

Page 36: ...ltekreislauf in dem das K hlmittel zirkuliert Das System funktioniert folgenderma en Der Kompressor CO verdichtet das K ltemittel und bringt es auf Hochdruck und Temperatur W hrend das warme Gas durc...

Page 37: ...TEMPERATURSONDE Eine Temperatursonde des Typs NTC ist an der Analogeinheit des elektronischen Controllers angeschlossen HOCHDRUCK SICHERHEITSDRUCKW CHTER Stoppt den Kompressorbetrieb wenn der Druck im...

Page 38: ...lang gedr ckt halten bis die blinkende Aufschrift POF erscheint Jetzt ist die Tastatur gesperrt und es k nnen nur der Sollwert die H chst und Mindesttemperatur angezeigt werden Um die Tastatur zu ent...

Page 39: ...Remote enable angeschlossen ist Maschinenstatus OFF ber Tastatur in diesem Fall schaltet sich das Gebl se nach Ablauf der Abschaltverz gerungszeit aus und nur wenn der Kompressor ausgeschaltet ist Al...

Page 40: ...Ausf hrungen f r den Fall dass der hiermit verbundene Kontakt ge ffnet wird muss der Controller den Kompressor und das Kondensatorgebl se deaktivieren Bei Vorliegen dieser Betriebsbedingung wird der...

Page 41: ...s HAUPTALARM Wenn ein Alarm ausgel st wird wird auf Display die entsprechende Meldung angezeigt und der Digitalausgang wechselt polig mit Umschaltkontakt max 8A Induktivit t 250 Vac Alarm auftritt auc...

Page 42: ...entfernten vorderen Teil wieder einsetzen und befestigen Die zuvor entfernte Gebl seplattewiedereinsetzen und befestigen den Das Frontpaneel wieder befestigen hierzu die Displaykabel Hinweis Um die Au...

Page 43: ...eschlossen f r die Versorgung der Einheiten mit 400V 50Hz ist auf die entsprechenden elektrischen Schaltpl ne Bezug zu nehmen Die angegebenen Nennspannungen haben eineToleranzvon 10 frequenztoleranz 2...

Page 44: ...latte wieder einsetzen das andere Kabelende an den Schl das Benutzersystem an die Parameter und anschlie en das Verfahren aus Kapitel 7 durchf hren um die Modbus Parameter zu ndern Installation der Fe...

Page 45: ...der Aufnahmetemperatur ist der s dreht sich Kompressor in die falsche Richtung und die Kontrollieren dass keine Alarme vorhanden sind Kontrollieren dass die Gebl se richtig funktionieren Kontrollieren...

Page 46: ...pr fen 11 3 GEFAHREN AUFGRUND VON ELEKTRISCHEN ST RUNGEN 11 3 1 SICHERHEITSVORSCHRIFTEN F R ELEKTRISCHE GER TE Einf hrung Die Ursachen von elektrischen Gefahren sind bekannt diese Gefahren k nnen durc...

Page 47: ...Ger t in nicht ausreichend gel fteten oder gro en R umen installiert wird und man merkt dass schnell K hlmittel austritt sollte sich das Personal entfernen und der Raum gel ftet Nicht angemessene Bef...

Page 48: ...der Verdampferventilator funktionieren der Kompressor funktioniert unregelm ig a Eingriff des Hochdruckw chters falls vorhanden Raumtemperatur ber dem maximal zugelassenen Wert siehe Typenschild Den...

Page 49: ...st eine Oberfl chenbehandlung mit Epoxybeschichtung Kondensatoren dagegen ist eine Beschichtung derOberfl chenerforderlich Ausf hrung Geschwindigkeitsregler Kondensatorgebl se SteuertdieGeschwindigkei...

Page 50: ...production et les manuels pr c dents sauf dans les cas exceptionnels Pour demander ou recevoir d ventuelles mises jour ou ajouts apport s au manuel d utilisation qui devront tre consid r s comme part...

Page 51: ...all es avec soin Contr lez imm diatement l unit d s que vous la recevez rifier qu elle a t transport e dans la bonne le sur le document de Nous vous conseillons d accepter la marchandise sous V rifiez...

Page 52: ...ompresseur CO comprime le gaz frigorig ne en l amenant une pression et temp rature lev es le gaz chaud en traversant le condensateur BC est refroidi et liqu fi en c dant de la chaleur l air ambiant Po...

Page 53: ...lateur condensateur lorsque la pression est inf rieure 8 5 bars il permet le fonctionnement du climatiseur une temp rature ambiante allant jusqu 20 C TRANSDUCTEUR DE PRESSION si pr sent Le transducteu...

Page 54: ...is es dans les diff rents r glages La liste des ressources est la suivante valeur sonde B1 valeur sonde B2 valeur sonde B3 valeur sonde B4 valeur sortie analogique AO1 valeur sortie analogique AO2 Uti...

Page 55: ...is il est n cessaire que le compresseur soit teint Smart Energy Management SEM Le ventilateur entre en mode SEM lorsque la temp rature est inf rieure ou gale au point de consigne de refroidissement de...

Page 56: ...tact qui lui est connect le contr leur d sactive le compresseur la r sistance chauffante si pr sente le ventilateur vaporateur et le ventilateur condensateur Dans cette condition on visualise l alarme...

Page 57: ...se former sur le compresseur et ressortir par les trous pr sents sur la que l armoire lectrique o l on veut appliquer le climatiseur ait un indice de protection IP54 ou plus que la tension disponible...

Page 58: ...u climatiseur deux tiges filet es males et deux crous ont t pr vues et doivent tre plac es dans les deux inserts sup rieurs du ch ssis en plus des vis standard afin de pouvoir accrocher le climatiseur...

Page 59: ...est indiqu e sur l tiquette situ e sur l unit et techniques au chapitre 15 Les tensions d alimentation peuvent tre 48VDC 36 59DC Pour les unit s pour les unit s pour les unit s triphas es Les unit s t...

Page 60: ...et faire passer la sonde par le trou r alis pr c demment dans la appliquer la proc dure de modification des param tres SEM2 ATTENTION N cessaire placer la sonde dans une zone concern e par la recircul...

Page 61: ...la garantie Afin de maintenir l efficacit et la s curit de l appareil les dessous devront effectu es tout au long de la intervention sur l unit veuillez couper l alimentation V rifier que l changeur...

Page 62: ...able doit insister sur l utilisation des mesures de s curit sans tol rer ni accepter d carts car cela peut provoquer des dommages aux personnes et aux appareils 11 3 3 HAUTE TENSION Tout contact avec...

Page 63: ...c s durant les op rations d entretien ordinaire ou Afin d effectuer les activit s d limination de fa on correcte et s re l op rateur doit se doter des EPI n cessaires qui sont gants anti coupure gants...

Page 64: ...onne le ventilateur ext rieur ne fonctionne pas le compresseur fonctionne par intermittence a Condensateur lectrique du ventilateur en panne Remplacez le condensateur lectrique b Ventilateur ext rieur...

Page 65: ...os de l unit pour afficher les informations concernant les conditions de travail Pour plus d informations se r f rer au chapitre Contr le et logique de fonctionnement Accessoire uniquement pour unit s...

Page 66: ...constructor aprecia mucho los avisos o propuestas sugeridos por instaladores o usuarios del producto para mejorar el contenido del presente manual S MBOLOS UTILIZADOS EN ESTE MANUAL PELIGRO RIESGO DE...

Page 67: ...ga franco f brica han sido individualmente controladas en todas sus Controle inmediatamente la pieza que acabe de recibir prestando atenci n al hecho de que se haya transportado en una posici n adecua...

Page 68: ...que se enfr a de dicha manera ESTRUCTURA Realizada con paneles autoportantes para garantizar una buena resistencia a la corrosi n se inspecciona f cilmente y garantiza al mismo tiempo una protecci n a...

Page 69: ...se utiliza para la transformaci n de la tensi nde redaaquellade losauxiliares AUTOTRANSFORMADOR si lo hubiera Se encuentra en los modelos que funcionan con tensi n bif sica 230 V y con tensi n trif s...

Page 70: ...SET En lo que concierne a las sondas B1 B2 B3 se podr visualizar un valor de temperatura expresado en grados Celsius o Fahrenheit El t rmino Err intermitente indica que la sonda presenta un error y el...

Page 71: ...los casos siguientes apertura del contacto conectado a la entrada digital Remote enable estado OFF de la m quina desde el teclado en este caso el ventilador se detiene al transcurrir el tiempo de ret...

Page 72: ...caso de aver a de la sonda cortocircuito o interrupci n el control espera un tiempo determinado desde el evento 10 segundos aproximadamente y luego desactiva todas las salidas digitales y anal gicas...

Page 73: ...esor que puede salir de los orificios presentes en la Que el armario el ctrico donde se desea instalar el intercambiador tenga un grado de protecci n IP54 o superior Que los orificios tornillos cables...

Page 74: ...montaje del intercambiador puntos b c ATENCI N No obstruya la circulaci n del aire aspirado o y expulsado del intercambiador Descarga de la condensaci n El tubo de descarga de la condensaci n debe est...

Page 75: ...ci n del intercambiador una protecci n magnetot rmica con curva en clase idad del instalador conforme a la EN 60335 1 60335 Para la elecci n del tipo de protecci n precedente al acondicionador UL haga...

Page 76: ...o minuciosamente antes de la puesta en funcionamiento de la unidad y si es necesario se debe contactar con el Servicio de Asistencia al Cliente de STULZ ATENCI N LateclaON OFF de lapantallaseusasolame...

Page 77: ...s unidades que contienen m s de 3 kg de refrigerante es obligado comprobar la ausencia de p rdidas de refrigerante seg n el Reglamento Europeo 842 2006 Los controles deben anotarse en el registro de l...

Page 78: ...DISPOSITIVO EST APAGADO Quite la alimentaci n de la unidad antes de intervenir Aseg rese de que despu s no haya tensi n en los circuitos Limpie y seque la zona de trabajo Quitar clavijas anillos estri...

Page 79: ...orio consultar al personal de referencia de la zona antes de empezar los trabajos La eliminaci n del embalaje de la unidad debe efectuarse Los embalajes de madera no est n tratados qu micamente a no s...

Page 80: ...TULZ SpA 3 El compresor y el ventilador externo funcionan el ventilador interno no funciona a El condensador el ctrico del ventilador no funciona Sustituya el condensador el ctrico del ventilador b Ve...

Page 81: ...uerto serial para MODBUS Puerto serial para la conexi n a un sistema de motorizaci n por medio del protocolo de comunicaci n Modbus RTU Sonda remota para la funci n SEM2 Sonda de sustituci n de la sum...

Page 82: ...CVE CVO 82 15 DATI TECNICI TECHNICAL DATA TECHNISCHE DATEN DONNEES TECHNIQUES DATOS T CNICOS Dati 230V UL a 60Hz data 230V UL at 60Hz daten 230V UL zu 60Hz donnees 230V UL 60Hz datos 230V UL en 60Hz...

Page 83: ...CVE CVO 83...

Page 84: ...CVE CVO 84...

Page 85: ...uissance sonore mesur selon la norme ISO 9614 2 avec des conditions normales d utilisation et dans des conditions de fonctionnement conformes Schalldruckpegel auf dem externen Kreislauf bezogen Aufgru...

Page 86: ...rd F r die CE Ausf hrung wird das Modell CVE CVO 05 08 als Beispiel gezeigt F r die UL Einheiten hingegen die Dichtung wie in der Abbildung dargestellt anbringen Hinweis A In der Abbildung wird der An...

Page 87: ...CVE CVO 87 CVE03 UL CVE 05 08 UL CVO 05 08 UL CVE 11 15 UL CVO 11 15 UL CVE20 UL CVO20 UL CVE 30 40 UL CVO 30 40 UL CVE60 UL CVO60 UL A A A B B B B B B B B...

Page 88: ......

Reviews: