68/88
Siemens Synco
900
CE1C2707en
Building Technologies
Function settings
05.07.2007
Room controller settings
These settings are displayed only when a user-defined room
type has been set (refer to “Configure rooms“, refer to page 16).
P-band Xp
The room controller’s P-band can be set for every room to suit indivi-
dual needs. For your guidance, refer to the standard settings:
Room type
Guide value Xp
Radiator heating slow
2 K
Radiator heating fast
2 K
Floor heating slow
2 K
Floor heating fast
2 K
Main menu > Heating > Room X > Room controller > P-band Xp:
Room
number
1 2 3 4 5 6
Room
name
Factory setting
2 K
2 K
2 K
2 K
2 K
2 K
Setting
Xp
Room
number
7 8 9 10 11
12
Room
name
Factory setting 2 K
2 K
2 K
2 K
2 K
2 K
Setting
Xp
Integral action time Tn
The room controller’s integral action time can be set for every room.
For your guidance, refer to the standard settings:
Room type
Guide value Tn
Radiator heating slow
5,400 s
Radiator heating fast
3,600 s
Floor heating slow
7,200 s
Floor heating fast
5,400 s
Main menu > Heating > Room X > Room controller >
Int action time Tn:
Room
number
1 2 3 4 5 6
Room
name
Factory setting 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s
Setting
Tn
Room
number
7 8 9 10 11
12
Room
name
Factory setting 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s
Setting
Tn
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......