36/88
Siemens Synco
900
CE1C2707en
Building Technologies
Commissioning the system
05.07.2007
Window / door state output
If at least one window / door is open, the respective output terminal is
closed. As a result, an open window / door can be shown via an addi-
tional external component.
State whether a window/door state output is used and how it is con-
trolled.
Setting Description
---
Inactive – window / door state output not
required
Via RF / S-Mode
Window / door state delivered via:
•
Relay output Qx of an RRV91…
heating circuit controller
•
S-Mode object on KNX TP1 *
Q1 (local)
Relay output Q1 of the central apartment
unit used as a window / door state output
* The connection of the relevant S-Mode objects of the central apartment
unit to the relevant S-Mode devices on KNX TP1 is made with a commis-
sioning tool (ETS)
Main menu > Commissioning > Basic configuration > Outputs >
Window / door state:
Factory setting
---
Your setting
---
Via RF / S-Mode
Q1 (local)
Configure RF repeaters
Activate the required number of RF repeaters. For that, select every
RF repeater required (1…3) and change the setting from “---“ to
”Active“.
Main menu > Commissioning > Basic configuration > RF repeater >
Repeater X:
Repeater 1
Repeater 2
Repeater 3
Factory setting
---
---
---
Your setting
---
Active
---
Active
---
Active
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......