DHW
Frost protection setpoint
Set the DHW setpoint to be used in Protection mode.
Main menu > DHW > Setpoints > Frost prot setp:
Guide value
5 °C
Your setting
Legionella setpoint
Set the setpoint the DHW storage tank should maintain during the
time the legionella function is performed.
Main menu > DHW > Legionella function > Legionella setpoint:
Guide value
70 °C
Your setting
Legionella protection frequency
Decide and set how often the legionella function should be activated.
It can be performed daily or weekly. With the weekly legionella func-
tion, the weekday can be selected (Mo..Su).
When using setting “Never“, the legionella function is always
deactivated.
Main menu > DHW > Legionella function > Legio prot freq:
Guide value
Monday
Your setting
Never
Daily
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Legionella protection time
Define the time of day (00:00..24:00) the legionella function should be
started.
Main menu > DHW > Legionella function > Legio prot time:
Factory setting
05:00
Your setting