73/88
Siemens Synco
900
CE1C2707en
Building Technologies
Function settings
05.07.2007
Charging time max
To prevent that – due to DHW priority – the heating circuit is restricted
or even locked for longer periods of time, “DHW charging with absolute
priority“ can be limited for a certain period of time (5..250 min).
With setting “---“, DHW charging takes place with no limitation
of the charging time.
Main menu > DHW > Settings > Charging time max:
Factory setting
60 min
Your setting
Forced charging
Normally, DHW storage tank charging is started only if the storage
tank temperature drops below the switch-on point (DHW storage tank
setpoint minus switching differential). Forced charging can enforce
storage tank charging, even if this switch-on criterion has not been
reached.
Starting
If forced charging is activated and the storage tank temperature lies
at least 1 K below the normal setpoint, forced charging is started.
Ending
Forced charging is ended when the normal setpoint is reached.
You can decide when forced charging is performed:
Never
Forced charging is deactivated (however, manual
triggering of forced charging is still possible via
the
DHW
button)
With the first
change to the
normal setpoint
Forced charging is performed when, for the first
time in a 24-hour period, the reduced setpoint
changes to the normal setpoint. As a result, the
DHW storage tank is completely charged at the
beginning of the day
With every
change to the
normal setpoint
Forced charging is performed every time the
reduced setpoint changes to the normal setpoint
Main menu > DHW > Settings > Forced charging:
Factory setting
Never
Your setting
Never
First change
Every change
One-time manual forced charging of the DHW storage tank
can also be triggered by a long push on the central apartment
unit’s
DHW
button. During manual forced charging, the DHW
symbol on the display blinks.
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......