Function settings
05.07.2007
Temperature request winter operation
This defines the validity of the space heating request during winter
operation:
Continuously: The heat request is constantly valid in winter operation.
Switching:
If the average valve position drops below a certain
value, the heat request is set invalid.
Main menu > Settings > Heat request > Temp request winter:
Factory setting
Switching
Your setting
Continuously
Switching
Temperature request 0..10 V
To be able to transmit a temperature request (for space heating and
DHW) to a heat demand controller by means of a 0..10 V signal, the
temperature setpoint at 0 V and 10 V must be predefined for the
central apartment unit. The values in between is interpolated in a
linear way. Temperature requests below the selected temperature
request threshold is not forwarded to the heat demand controller (0 V).
Main menu > Settings > Heat request > Temp request 0 V:
Main menu > Settings > Heat request > Temp request 10 V:
Main menu > Settings > Heat request > Temp request thresh:
DC 0..10 V
0
2
4
6
8
10
10
20
30
40
50
60
70
80
90 100 110 120
°C
27
07
Z
3
2
3
2
1
0
c
Value in °C at DC 0 V
d
Value in °C at DC 10 V
e
Threshold value of temperature request (temperatures below this level are interpreted
as “No demand for heat”)
Factory setting
Your setting
Temperature request at 0 V
0 °C
Temperature request at 10 V
100 °C
Temperature request threshold
0 °C
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......