Commissioning the system
05.07.2007
State whether an apartment pump is used and how it is controlled.
Setting Description
---
Inactive – no apartment pump installed
Via RF
Apartment pump connected to relay output Qx
of an RRV91… heating circuit controller
Q1 (local)
Apartment pump connected to relay output Q1
of the central apartment unit
Main menu > Commissioning > Basic configuration > Outputs >
Apartment pump:
Factory setting
---
Your setting
---
Via RF
Q1 (local)
Summer operation
When the respective output terminal closes, changeover of the cen-
tral apartment unit to summer operation can be communicated to
external components / controllers.
State whether a summer operation relay is used and how it is con-
trolled.
Setting Description
---
Inactive – summer operation relay not
required
Via RF / S-Mode
Summer operating state delivered via:
•
Relay output Qx of an RRV91…
heating circuit controller
•
S-Mode object on KNX TP1 *
Q1 (local)
Relay output Q1 of the central apartment
unit used as a summer operation relay
* The connection of the relevant S-Mode objects of the central apartment
unit to the relevant S-Mode devices on KNX TP1 is made with a commis-
sioning tool (ETS)
Main menu > Commissioning > Basic configuration > Outputs >
Summer operation:
Factory setting
---
Your setting
---
Via RF / S-Mode
Q1 (local)
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......