Legionella protection period
When the legionella function is active, the DHW storage tank is
maintained at the legionella protection setpoint for the period of time
set here (0.00 – 6.00 hours).
Main menu > DHW > Legionella function > Legio prot period:
Guide value
00.30 h.min
Your setting
DHW priority
With DHW priority, preference can be given to DHW storage tank
charging by reducing the amount of heat delivered to the heating
circuits.
No priority
During DHW heating, there is no restriction with regard to the amount
of heat delivered to the heating circuits.
The highest temperature request (space heating or DHW) is sent to
the heat demand controller.
Absolute priority
During DHW heating, the heating circuits are not allowed to draw any
heat.
The temperature request for DHW charging is sent to the heat de-
mand controller.
Main menu > DHW > Settings > Priority:
Factory setting
Absolute
Your setting
None (parallel)
Absolute
In the case of DHW heating with a diverting valve, set the
DHW priority to "Absolute".
Switching differential
The switching differential is used to control DHW charging. Charging
is enabled when the DHW temperature drops below the DHW set-
point by the amount of the switching differential (1..20 K) set here.
Charging is stopped as soon as the DHW setpoint is reached again.
Main menu > DHW > Settings > Switching diff:
Factory setting
5 K
Your setting
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......