32/88
Siemens Synco
900
CE1C2707en
Building Technologies
Commissioning the system
05.07.2007
Heat demand relay
When the appropriately defined output terminal closes, a heat de-
mand signal is transmitted to the heat source.
State whether a heat demand relay is used and how it is controlled.
Setting Description
---
Inactive – heat demand relay not
required
Via RF
Relay output Qx of an RRV91… heat-
ing circuit controller used as a heat de-
mand relay
Q1 (local)
Relay output Q1 of the central apart-
ment unit used as a heat demand relay
Main menu > Commissioning > Basic configuration > Outputs >
Heat demand relay:
Factory setting
---
Your setting
---
Via RF
Q1 (local)
Heat demand 0..10 V
The current heat demand can be transmitted to the heat source in the
form of a 0..10 V signal.
The temperature values corresponding to 0 V and 10 V and the
threshold value for a valid heat request can be set (refer to page 78).
State whether the 0..10 V heat demand output is used and how it is
controlled.
Setting Description
---
Inactive – 0..10 V heat demand output
not required
Via RF
Universal output U of the RRV912…
heating circuit controller used as a
0..10 V heat demand output
Main menu > Commissioning > Basic configuration > Outputs >
Heat dem 0..10 V:
Factory setting
---
Your setting
---
Via RF
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......