69/88
Siemens Synco
900
CE1C2707en
Building Technologies
Function settings
05.07.2007
Derivative action time Tv
The room controller’s derivative action time can be set for every
room. For your guidance, refer to the standard settings:
Room type
Guide value Tv
Radiator heating slow
450 s
Radiator heating fast
540 s
Floor heating slow
540 s
Floor heating fast
540 s
Main menu > Heating > Room X > Room controller >
Der action time Tv:
Room
number
1 2 3 4 5 6
Room
name
Factory setting 450 s
450 s
450 s
450 s
450 s
450 s
Setting
Tv
Room
number
7 8 9 10 11
12
Room
name
Factory setting 450 s
450 s
450 s
450 s
450 s
450 s
Setting
Tv
Neutral zone
For rooms using 3-position actuators, the room controller’s neutral
zone (0..20 K) can be set for every room. For your guidance, refer to
the standard settings:
Room type
Guide value neutral zone
Radiator heating slow
0.1 K
Radiator heating fast
0.1 K
Floor heating slow
0.1 K
Floor heating fast
0.1 K
Main menu > Heating > Room X > Room controller > Neutral zone:
Room
number
1 2 3 4 5 6
Room
name
Factory setting
0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
Setting
Neut.
Room
number
7 8 9 10 11
12
Room
name
Factory setting 0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
Setting
Neut.
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......