Function settings
05.07.2007
Setpoint boost DHW charging
To make possible DHW charging, the flow temperature must be
higher than the required DHW setpoint. Set the required setpoint
boost here (0..50 K).
Main menu > DHW > Settings > Setp incr DHW charg:
Factory setting
10 K
Your setting
System pump required
If the system pump is controlled by a KNX TP1-compatible controller,
it can be selected whether the system pump should run during DHW
charging (depending on the selected type of plant).
31
31
S
59
A
B
Case A System pump required for DHW charging (system pump: Yes)
Case B System pump not required for DHW charging (syst. pump: No)
Main menu > DHW > Settings > System pump:
Factory setting
Yes
Your setting
Yes
No
Summer operation electric immersion heater
Decide whether the DHW time switch should be used for controlling
the electric immersion heater.
Without time
switch
The time switch has no impact on the control of
the electric heater in the summer. The DHW
temperature is maintained at the normal setpoint.
With time
switch
For control of the electric heater in the summer,
the controller gives consideration to the time
switch and the holiday program. The DHW
operating mode must be set to ”Auto“.
Main menu > DHW > Settings > Su op el imm heater:
Factory setting
With time switch
Your setting
Without time switch
With time switch
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......