Building Technologies
Commissioning the system
05.07.2007
Main menu > Commissioning > Basic configuration > Faults >
Fault input X:
Fault input
Factory setting
Your setting
1 ---
---
Via RF / S-Mode
B (local)
2 ---
---
Via RF / S-Mode
B (local)
3 ---
---
Via RF / S-Mode
B (local)
4 ---
---
Via RF / S-Mode
B (local)
Fault outputs 1 and 2
If system faults occur, they can be forwarded to an external
component by closing a fault output.
You can select the fault priority and origin of fault for the relay to
close. For a description of these settings, refer to the Operating
Instructions, section “Faults“.
State whether a fault output is used and how it should be controlled.
Setting Description
---
Inactive – fault output not required
Via RF
Relay output Qx of an RRV91…
heating circuit controller used as a
fault output
Q1 (local)
Relay output Q1 of the central
apartment unit used as a fault output
Main menu > Commissioning > Basic configuration > Faults >
Fault output X:
Fault output
Factory setting
Your setting
1 ---
--- (none)
Via RF
Q1 (local)
2 ---
--- (none)
Via RF
Q1 (local)
Configure inputs
By closing a contact at the input terminal, the respective input func-
tion can be triggered.
Activate the respective input function by stating from where the cen-
tral apartment unit receives the signal of the input terminal
(---, Via RF / S-Mode, B (local)).
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......