35/88
Siemens Synco
900
CE1C2707en
Building Technologies
Commissioning the system
05.07.2007
Status output
When the appropriate output terminal closes, the central apartment
unit indicates the occurrence of events via an external component
(e.g. signal lamp or horn).
The events (smoke, window, fault inputs 1 - 4) leading to closure of
the status output can be defined via parameter “Events status out-
put“. For a description of this parameter, refer to the Operating In-
structions, section “Supervision“.
State whether a status output is used and how it is controlled.
Setting Description
---
Inactive – status output not required
Via RF / S-Mode
Deliver state of status output via:
•
Relay output Qx of an RRV91…
heating circuit controller
•
S-Mode object on KNX TP1 *
Q1 (local)
Relay output Q1 of the central apartment
unit used as a signal output
* The connection of the relevant S-Mode objects of the central apartment
unit to the relevant S-Mode devices on KNX TP1 is made with a commis-
sioning tool (ETS)
Main menu > Commissioning > Basic configuration > Outputs >
Status output:
Factory setting
---
Your setting
---
Via RF / S-Mode
Q1 (local)