Terminal
Function
Technical specifications
Stripped length
12 mm (0.47 inch)
Tool
Slotted screwdriver, 1.0 x 5.5 mm
Tightening torque
1.2 ... 1.5 Nm (10.6 lbf in)
6.2.1.2
Preparing the power cables
Observe the following stripped lengths when connecting the connection plug and the cable
shield.
①
Insulated conductors U-V-W
②
Protective insulated conductor
③
Braided shield
④
Shrink sleeving
Table 6-13
Insulated conductor and stripped lengths as a function of the cable cross-section, data in mm and (inch)
Connection
6 mm² AWG 10
10 mm
2
/ 16 mm
2
AWG 8 / AWG 6
a
b
a
b
U1
90 +2/-3
(3.54+0.08/-0.12)
12 ±0.5
(0.47 ±0.02)
90 +2/-3
(3.54+0.08/-0.12)
15 ±0.5
(0.59 ±0.02)
V1
W1
Protective conductor
95 +2/-3
(3.74 +0.08/-0.12)
12 ±0.5
(0.47 ±0.02)
95 +2/-3
(3.74 +0.08/-0.12)
15 ±0.5
(0.59 ±0.02)
Prepare the power cables as follows:
1. Remove the cable sheath to a length of 90 mm (3.54 in) with a tolerance of ±5 mm (±0.20 in).
2. Fold back the braided shield.
3. Fix the braided shield. Preferably use shrink sleeving with hot melt adhesive.
4. Shorten the single wires as specified in the table.
5. Strip the insulation from the single wires as specified in the table.
6. Use end sleeves according to DIN 46228 with the appropriate cross-section.
Accessories
6.2 Accessories for Smart Line Modules
Booksize power units
92
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0