Line and load connections
Table 4-6
Line and load connections, line reactors for Smart Line Modules
Article number
6SL3100-
6SL5100-
0EE21-6AA0
0EE21-6AD0
0EE22-4AC0
0EE22-4AD0
Line connection
Load connection
1U1, 1V1, 1W1
1U2, 1V2, 1W2
L1, L2, L3
L1.2, L2.2, L3.2
L1, L2, L3
L1.2, L2.2, L3.2
L1, L2, L3
L1.2, L2.2, L3.2
Terminals
Line connection and load
connection
Screw terminals
10 mm
2
(AWG 8)
1.5 … 1.8 Nm
(15.9 lbf in)
Screw terminals
16 mm
2
(AWG 10)
2.5 Nm (22.1 lbf in)
Screw terminals
16 mm
2
(AWG 10)
2.5 Nm (22.1 lbf in)
Screw terminals
16 mm
2
(AWG 10)
2.5 Nm (22.1 lbf in)
Protective conductor con‐
nection
Terminal studs M6
1)
Screw M6
6 Nm (53.1 lbf in)
Screw M6
6 Nm (53.1 lbf in)
Screw M6
6 Nm (53.1 lbf in)
1)
For ring cable lugs without insulation
4.6.4
Dimension drawings
$
&
%
'
)
(
Figure 4-4
Dimension drawing of line reactors for 16 kW and 24 kW Smart Line Modules, all dimensions
in mm and (inches)
Article number
Dimensions, all dimensions in mm and (inches)
A
B
C
D
E
F
mm
in
mm
in
mm
in
mm
in
mm
in
mm
in
6SL3100-0EE21-6AA0
219
8.62
110.5 4.35
176
6.93
201
7.91
80.5
3.17
7.0 x
13
0.28
x 0.51
6SL5100-0EE21-6AD0
6SL5100-0EE22-4AC0
219
8.62
126
4.96
195
7.68
201
7.91
96
3.78
7.0 x
13
0.28
x 0.51
6SL5100-0EE22-4AD0
Line connection and line-side power components
4.6 Line reactors
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
51