The components are normally used in machines. The assessment and testing is based on
DIN EN 12198.
Table 8-4
Information for frequency range 0 Hz to 300 GHz
Frequency range
0 Hz ... 100 kHz
100 kHz ... 300 GHz
Electric field strength
Limits not exceeded
Limits not exceeded
Magnetic flux density
For assessment, see the following
table
Limits not exceeded
Table 8-5
Minimum clearances to SINAMICS S220 power units at 0 Hz ... 100 kHz in cm (inch)
Power of the
Line Module
Generally
Individuals with active implants
Control cabinet
closed
Control cabinet
open
Control cabinet
closed
Control cabinet
open
P ≤ 36 kW
0 (0)
10 (4)
The limit of 100 µT
(RMS) at 50 Hz is not
exceeded. Must be sep‐
arately assessed de‐
pending on the active
implant.
Must be separately
assessed depending
on the active im‐
plant.
Note
The minimum distances indicated above apply to the head and complete torso of the human
body. Shorter distances are possible for extremities.
Control cabinet design and EMC booksize
8.4 Electromagnetic fields at the workplace
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
117