WARNING
Spread of fire from built-in devices
In the event of fire outbreak, the enclosures of built-in devices cannot prevent the escape of
fire and smoke. This can result in serious personal injury or property damage.
• Install built-in units in a suitable metal cabinet in such a way that personnel are protected
against fire and smoke, or take other appropriate measures to protect personnel.
• Ensure that smoke can only escape via controlled and monitored paths.
WARNING
Active implant malfunctions due to electromagnetic fields
Converters generate electromagnetic fields (EMF) in operation. Electromagnetic fields may
interfere with active implants, e.g. pacemakers. People with active implants in the immediate
vicinity of an converter are at risk.
• As the operator of an EMF-emitting installation, assess the individual risks of persons with
active implants.
• Observe the data on EMF emission provided in the product documentation.
WARNING
Unexpected movement of machines caused by radio devices or mobile phones
Using radio devices or mobile telephones in the immediate vicinity of the components can
result in equipment malfunction. Malfunctions may impair the functional safety of machines
and can therefore put people in danger or lead to property damage.
• Therefore, if you move closer than 20 cm to the components, be sure to switch off radio
devices or mobile telephones.
• Use the "SIEMENS Industry Online Support app" only on equipment that has already been
switched off.
NOTICE
Damage to motor insulation due to excessive voltages
When operated on systems with grounded line conductor or in the event of a ground fault in
the IT system, the motor insulation can be damaged by the higher voltage to ground. If you use
motors that have insulation that is not designed for operation with grounded line conductors,
you must perform the following measures:
• IT system: Use a ground fault monitor and eliminate the fault as quickly as possible.
• TN or TT systems with grounded line conductor: Use an isolating transformer on the line
side.
Fundamental safety instructions
2.1 General safety instructions
Booksize power units
18
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0