6. Break out the cutout in the protective flap.
Mounted DC link adapter with closed protective
flap.
6.1.6.4
DC link adapter (6SL3162-2BM01-0AA0)
Preparing the DC link connecting cables
To connect the various sub lineups, use shielded single wires that are mechanically secured.
1. Prepare the DC link connecting cables as shown below.
A
30 (1.18)
A
30 (1.18)
1
2
1
2
①
Braided shield folded back and fixed using shrink sleeving
②
Insulated end sleeve
Figure 6-4
Single-core and two-core DC link connecting cable with insulated end sleeves, all
dimensions in mm and (inch)
2. Only use shielded cables with insulated end sleeves.
Refer to the table below for dimension A:
Conductor cross-section
[mm
2
]
Mounting location of the DC link
adapter at the drive lineup
Connection
A [mm]
35 / 50 / 70 / 95 / 120
Left / right
DCP
60
DCN
70
Accessories
6.1 DC link adapter
Booksize power units
86
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0