Installation altitude
Operation
0 ... 1000 m above sea level without derating
> 1000 ... 2000 m
• Reduction of the output current by 10 % per 1000 meters, or
• Reduction in the ambient temperature by 5 °C per 1000 meters
> 2000 ... 4000 m
• Reduction of the output current by 10 % per 1000 meters, or
• Reduction in the ambient temperature by 5 °C per 1000 meters
• Operation on line supply systems with grounded neutral point, or
• Operation on an isolating transformer with secondary grounded neutral point
1)
Product packaging (storage packaging) is individual packaging for storage and does not satisfy the requirements for
transport. As a consequence, product packaging is therefore not suitable for shipping.
2)
Transport packaging is either packaging that is directly suitable for transport, or secondary packaging which, together with
the product packaging, satisfies the requirements for transport.
Table 3-5
Certificates
Declarations of conformity
EU Declaration of Conformity (Low Voltage Directive, EMC, Machinery Directive, RoHS),
China RoHS, RCM, Morocco
Certifications
cULus, cURus, KC, EAC, UKCA
System overview
3.4 S220 components and system data
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
35