The optional shield connection plate has several slots, which provide various options for the
shield support:
Table 6-16
Accessories for the shield support - shield connection clamp
Article number and designation
Recommended cable di‐
ameter
Torque
up to 20 mm
0.8 Nm (7.08 lbf in)
8WH9130-0NA00
Phoenix SK28
from more than 20 mm to a
maximum of 35 mm
1.8 Nm (15.93 lbf in)
8WH9130-0PA00
Phoenix SK35
Mounting the optional shield connection plate
The connecting cable shield is attached to the shield connection plate of the Smart Line Module
using the supplied shield connection clamp.
Required tool:
• T20 Torx screwdriver for the shield connection plate
1. Fasten the shield connection plate to the lower mounting points of the strain relief plate.
2. Tighten the two screws with a torque of 3 Nm (26.6 lbf in).
3. Insert the connection plug into connection socket X1 at the Smart Line Module until it snaps
into place. The plug has been completely inserted once you hear it snap into place.
Accessories
6.2 Accessories for Smart Line Modules
Booksize power units
98