Immunity for a drive system equipped with SINAMICS S220 components
Note
Integrating SINAMICS S220 components in other plants/machines
When variable-speed drive systems are integrated in other plants/machines, additional
measures may be required in order to comply with their product standards.
With respect to the compliance with limits for harmonic currents, EMC product standard
IEC 61800‑3 for drive systems (PDS) refers to compliance with standards IEC 61000‑3‑2 and
IEC 61000‑3‑12. Converters are classified as equipment used on a professional basis, deployed
in certain areas of business and industry - and are not operated in the general public domain.
Observe the following conditions when using the system in the first environment:
• The drive system must be installed in compliance with EMC regulations by appropriately
trained professionals.
• The converters must be equipped with a Category C2 line filter.
• The device-specific information and instructions for maintaining harmonic current limits
must be complied with.
Note
Malfunctions when not using original Siemens accessories
Malfunctions can occur if accessories are used that are not original.
• For DRIVE-CLiQ connections, only use the genuine Siemens DRIVE-CLiQ wiring and DRIVE-
CLiQ cabinet bushings.
Note
Faulty operation of the machine due to incorrect shielding or cables that are too long
The machine can malfunction if the shielding is incorrect or the cables are too long.
• Always follow the correct procedures for shielding and permissible cable lengths.
Control cabinet design and EMC booksize
8.3 Electromagnetic compatibility
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
115