Required tool:
• Torx screwdriver T20
1. Loosen the DC link screws.
2. Turn over the DC link bridge.
3. Tighten the DC link screws with a tightening torque of 1.8 Nm (15.9 lbf in). It is essential that
you follow the sequence shown below (1) and (2).
4. On the right-hand side of the component (3) located to the far right, tighten the DC link screw
with a tightening torque of 1.8 Nm (15.9 lbf in). The electrical connection from the DC link
busbar to the component is now established.
1. Connection of the lower DC link busbars
2. Connection of the upper DC link busbars
Connection of the 24 V busbars
The 24 V busbars of the components are connected using the 24 V connectors. The 24 V
connectors are provided in the accessories pack.
• Plug a 24 V connector onto each of the 24 V busbars between the Line Module, Motor Module
and DC link component.
• All of the 24 V connectors must be inserted before commissioning.
WARNING
Fire hazard for 24 V connectors and unconnected DC link busbars
For drive lineups in series, whose DC link busbars are not connected with one another, it is not
permissible to insert 24 V connectors between these drive lineups. Otherwise the 24 V
connectors can burn and cause severe injury or death as result of fire or smoke.
• If the DC link busbars of the components are not connected with one another, then you
must use a 24 V terminal adapter for each component to establish the 24 V supply.
NOTICE
Damage to the 24 V connector as a result of incorrect insertion/withdrawal
Incorrect insertion/withdrawal of a 24 V connector can damage it.
• It is only permissible to withdraw or insert 24 V connectors a maximum of 5 times.
Control cabinet design and EMC booksize
8.7 Electrical connection
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0