Table 3-19
FB_CommonPLCToAddOn connections
Name
Type Data
type
Unit-global variables of "AddOn"
Meaning
Common_IO_PIW
IN
ARRAY
[0..11]
OF word
addon_common_receive
Input array for the Common
b16_stw1
OUT WORD
-
Control word 1 output not sep‐
arated into individual bits
bo_stw_1_Man_Fixobst_Off
OUT BOOL
common_plc_man_fixobst_off
Bit 0 of control word 1
bo_stw_1_Man_Varobst_Off
OUT BOOL
common_plc_man_varobst_off
Bit 1 of control word 1
bo_stw1_No_Wait_Pos
OUT BOOL
common_plc_no_wait_pos
Bit 2 of control word 1
bo_stw1_Hoist_Man
OUT BOOL
common_plc_hoist_man
Bit 3 of control word 1
bo_stw1_Locked_Bit0
OUT BOOL
common_plc_locked_bit0
Bit 4 of control word 1
bo_stw1_Locked_Bit1
OUT BOOL
common_plc_locked_bit1
Bit 5 of control word 1
bo_stw1_Slackrope
OUT BOOL
common_plc_slackrope
Bit 6 of control word 1
bo_stw1_Bayscanner_Valid
OUT BOOL
common_plc_bayscanner_valid
Bit 7 of control word 1
bo_STW1_Learn_Profil_On
OUT BOOL
common_plc_learn_profil_on
Bit 8 of control word 1
bo_STW1_Learn_Profil_Reset
OUT BOOL
common_plc_learn_profil_reset
Bit 9 of control word 1
bo_stw1_Dig_Hoist_Dist_Corr
OUT BOOL
common_plc_dig_hoist_dist_corr
Bit 10 of control word 1
bo_stw1_Start_2D_Calc
OUT BOOL
common_plc_start_2d_calc
Bit 11 of control word 1
bo_STW1_Spreaders_Coupled
OUT BOOL
common_plc_Spreaders_Coupled
Bit 12 of control word 1
bo_stw1_impnt_ext_active
OUT BOOL
common_plc_Impnt_Ext_Active
Bit 13 of control word 1
bo_stw1_save_logger
OUT BOOL
common_plc_Save_Logger
Bit 14 of control word 1
i16Load
OUT INT
common_plc_load
Weight of the load
i32Value_Bayscanner
OUT DINT
common_plc_value_bayscanner
Bay scanner value
i32Count_Bayscanner
OUT DINT
common_plc_count_bayscanner
Bay scanner counter
i8ParSet
OUT SINT
common_plc_ParSet
Parameter set
i16DS_Width
OUT INT
common_plc_DS_Width
Overall width in double-
spreader operation
i32impnt_ext
OUT DINT
common_plc_Impnt_Ext
External immersion point
from PLC
Task
The "FB_CommonPLCToAddOn" block reads the input area from the PROFIBUS DP /
PROFINET PN for the Common block and separates the array into words and bits.
Connections
The outputs must be connected using unit-global variables of the "AddOn" MCC source file with
the inputs of the DCC_SCCOMMON DCC block.
Overview of the software
3.3 Sway control function blocks