No
.
Items
What needs to be checked?
o.k.
8
Manual operation for TLS cylinders
(external hydraulic system)
● Commissioning
● Functional capability
● External engineering
● Safety functions (as under No. 2)
9
Spindle of the skew drive
● Position sensing
● Position monitoring
● Homing
10 Skew drive including coupled mechanical
components
● Optimization of speed controller [Ref.
2 Chapter 8.6]
(requirement for position control function‐
ality in the software)
9.7.2
Activation of TLS function and skew drive
To be able to operate the electrical system and the position sensing function of the hydraulic
system, the TLS function and the skew drive must be activated with the following parameter
settings:
● P240 = 1 (activate TLS function)
● P320 = 1 (release skew drive)
● P321 = 1 (cylinder control disabled)
If these parameters are not correctly set, some screens and parameter groups might not be
displayed at all or might appear as incomplete displays.
9.7.3
Commissioning cylinders and electric drive
To commission the cylinders and the electric drive, follow the instructions in these chapters:
1. See: Parameterization of the actual positions (Page 351)
2. See: Conversion of cylinder positions, angle of rotation (Page 357)
3. See: Calculating the effective pendulum length for the skew oscillation (Page 357)
4. See: Evaluation of the current position of the skew drive spindle (Page 363)
5. See: Position controller setting (P328) (Page 364)
6. See: Setting the limit for set position P324 (Page 365)
7. See: Kinematic transformation of skew drive position, angle of rotation (Page 365)
8. See: Parameterization of skew damping (Page 366)
Commissioning AddOn Software
9.7 Commissioning TLS (skew damping with electric drive only)
SC integrated STS, GSU
368