P75 Horizontal trolley travel to the hopper (GSU)
Travel length over the hopper without hoist movement.
Value 1 activates automatic calculation.
The parameter is operative only when on-the-fly unloading has been activated. This means:
● On-the-fly unloading is enabled with parameter P152 (selection 3 = ON).
● The Flying control bit is set.
● The time-optimized control method is selected.
Default: 1 [mm]
min: 0 [mm]
max: 100000 [mm]
Access code: 1
Display: Only for GSU (P102, selection 0 = ON)
P76 Horizontal travel to the ship (GSU)
Setting of the travel length over the hopper without hoist movement.
Value 1 activates automatic calculation.
The parameter is operative only when the following conditions are fulfilled:
● On-the-fly unloading was active during the previous travel operation to the hopper.
● The TRAVEL control bit was not reset between the previous and current travel operations.
Default: 1 [mm]
min: 0 [mm]
max: 100000 [mm]
Access code: 1
Display: Only GSU
P77 Range for closing the brake, hoist (SAM)
The direction signals are reset if the absolute value of the difference between the target and the
actual position is less than this value and the "ZERO" speed has been reached (P44).
Default: 200 [mm]
min: 10 [mm]
max: 1000 [mm]
Access code: 2
Display: Always
P78 Safety clearance, hoist (MAN)
This parameter is used to define the safety clearance in the hoist direction and is only operative
in MAN mode.
Default: 500 [mm]
min: 0 [mm]
max: 10000 [mm]
Access code: 1
Display: Always