Step 5: Checking values in the SIMOCRANE CeCOMM diagnostic program
Correct data exchange must be checked on display screens 1 to 3 of the SIMOCRANE
CeCOMM diagnostic program. The displayed values are used and processed in the sway
control system. It is also necessary to check that the output data of the sway control system,
such as the output velocities and status bits, are correctly returned to the SIMATIC S7.
Configuration
5.17 Communication tests for the STS application project
SC integrated STS, GSU
Operating Instructions, 07/2019, A5E48271265B AA
145