9.3.6
Checking of the communication between PLC and SIMOTION
The SIMOCRANE CeCOMM diagnostic program has various display screens in which
communication functions can be checked. The "PLC-Interface" display screen is called up from
the main menu or from another display screen using the "2" key for this purpose.
Figure 9-2
Monitor function, "PLC-Interface" display screen
The current input and output data of the sway control system are shown on this display screen.
The data must first be checked for correctness.
Note
Note about the set position (reference position; see figure above)
If parameter P102=1 (selection STS), the following exception applies:
If S_SET=0, the target position from the target generator is displayed.
External and internal targets are displayed in different ways in SIMOCRANE CeCOMM, see
Chapter Selecting external and internal targets (Page 342).
The "Status of the drives [3]" display screen is called with the "3" key (see screenshot below).
The command and status bits are displayed here. They should also be checked for correct
assignment before the next commissioning step is taken. The color differences in the display
of the actual values show which values or states are OK or active (green).
Note
Red display indicates an error or stop in the system, "Not released," "Stop," "Off," etc.
Commissioning AddOn Software
9.3 Commissioning requirements for AddOn software
SC integrated STS, GSU
324