98/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
8 AGM60...
25.09.2013
8.3 Connecting cable between AGM60... and
LMV36... basic unit (AGV61.100 cable)
This cable is required when, due to the selected type of fuel train (refer to chapter
Selection of operating mode
), 2 fuel actuators are needed.
For that, the 2 fuel actuators must be connected to terminals X54a and X54b of the
AGM60... The AGV61.100 cable is required for making the electrical connection
between the 2 fuel actuators and the basic unit.
If only 1 fuel actuator is used, it must be connected directly to the basic unit.
Connection plug assignment of cable:
1 = pink or alternatively red
2 = white or alternatively black
3 = brown
4 = grey
5 = yellow
6 = green