28/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
4 Technical data
25.09.2013
4 Technical
data
4.1 LMV36...
basic
unit
Mains voltage
AC 120 V -15 % / +10 %
Mains frequency
50 / 60 Hz ±6 %
Power consumption
<30 W (typically)
Safety class
I, with parts according to II and III to
DIN EN 60730-1
Degree of protection
IP00
Note
The burner or boiler manufacturer must
ensure degree of protection IP40 for the
LMV36... as per DIN EN 60529 through
adequate installation
4.1.1 Terminal loading
Inputs
Perm. mains primary fuse
(externally)
Max. 16 AT
Unit fuse F1 (internally)
6.3 AT (DIN EN 60127 2 / 5)
Mains supply: Input current depending on the operating state of the unit
Undervoltage
Safety shutdown from operating
position at mains voltage
Approx. AC 93 V
Restart on rise in mains voltage
Approx. AC 95 V
Status inputs: Status inputs (with the exception of the safety loop) of the contact
feedback network (CFN) are used for system supervision and require mains-related
input voltage
Input safety loop
Refer to
Terminal loading outputs
Input currents and input voltages
- UeMax
- UeMin
- IeMax
- IeMin
UN +10 %
UN -15 %
1.5 mA peak
0.7 mA peak
Contact material recommendation
for external signal sources (LP,
Pmin, Pmax, etc.)
Gold-plated silver contacts
Transition / settling behavior /
bounce
- Perm. bounce time of contacts
when switching on / off
Max. 50 ms
(after the bounce time, contact must stay
closed or open)
UN
AC 120 V
Voltage
detection
- On
- Off
AC 90...132 V
<AC 40 V