13/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
1 Safety notes
25.09.2013
The plugs of the connecting cables for the LMV36… or other accessories, such as
the OCI410... interface (plugged into the BCI), may be removed or exchanged only
when the plant is shut down (all-polar disconnection), since the BCI does not
provide safe separation from mains voltage.
The connection for the SQM3… or SQN1... actuators does not provide safe
separation from mains voltage. Prior to connecting or changing one of these
actuators, the plant must be shut down (all-polar disconnection)
When setting up a system with the AGM60..., check to ensure that the sensors and
actuators are correctly assigned to fuels
To ensure safety and reliability of the LMV36... and the AGM60..., the following points
must also be observed:
-
Condensation and ingress of humidity must be avoided. Should such conditions
occur, make sure that the unit is completed dry before switching on again!
-
Static charges must be avoided since they can damage the unit’s electronic
components when touched.
Recommendation:
Use ESD equipment
-
If the unit fuse was blown due to overload or a short-circuit at the connection
terminals, the LMV36... must be replaced since the switching contacts could have
been damaged