24.1.2.3. List of phase displays
Phase Function
Ph00 Lockout
phase
Ph02 Safety
phase
Ph10 Home
run
Ph12 Standby
(stationary)
Ph22
Fan ramp up time (122) (fan motor = ON, safety valve = ON)
Ph24
Traveling to the prepurge position
Ph30 Prepurge
time
Ph36
Traveling to the ignition position
Ph38 Preignition
time
Ph39
Valve proving filling time
(test pressure-switch-min when mounted between fuel valve V1 and fuel valve V2)
Ph40
1st safety time (ignition transformer ON)
Ph42
1st safety time (ignition transformer OFF),
Ph44 Interval
1
Ph50 2nd
safety
time
Ph52 Interval
2
Ph60
Operation 1 (stationary)
Ph62
Max. time low-fire (operation 2, preparing for shutdown, traveling to low-fire)
Ph70 Afterburn
time
Ph72
Traveling to the postpurge position
Ph74
Postpurge time (no extraneous light test)
Ph78
Postpurge time 3 (abortion when load controller ON)
Ph80
Valve proving evacuation time
Ph81
Valve proving test time atmospheric pressure, atmospheric test
Ph82
Valve proving filling test, filling
Ph83
Valve proving test time gas pressure, pressure test
Ph90
Gas shortage waiting time