
114/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
11 Electronic fuel-air ratio control
25.09.2013
11.3.5 Limitation of modulation range
If the modulation range shall be further restricted from 20 to 100% against the defined
curve, 4 parameters are available to define a new low-fire and high-fire position.
No. Parameter
545
Lower output limit
undefined = 20 %
565
Fuel 1: Lower output limit
undefined = 20 %
546
Upper output limit
undefined = 100 %
566
Fuel 1: Upper output limit
undefined = 100 %
20
% L
ow
-fi
re
Low
e
r output
lim
it P5
45
Uppe
r o
ut
put
lim
it P
54
6
10
0 %
Hi
g
h-f
ire
VSD
Figure 75: Restriction of modulation range